308A.1.1.1.6 Buildings Removed From Hospital Service
JUMP TO FULL CODE CHAPTER
The means of egress for acute care hospitals shall be permitted to pass through buildings that are removed from hospital service only if the buildings remain under the jurisdiction of OSHPD, and only until January 1, 2030, subject to the following:
- Egress for conforming hospital buildings shall be permitted to pass through buildings that have been removed from acute care hospital service that comply with the requirements of Section 308A.1.1.1.1 or 308A.1.1.1.3.
- Egress for nonconforming hospital buildings shall be permitted to pass through buildings that have been removed from acute care hospital service that comply with the requirements of Section 308A.1.1.1.2 or 308A.1.1.1.4.
After January 1, 2030, the means of egress for acute care hospital buildings shall only pass through hospital buildings that have approved performance categories of SPC-3 or higher and NPC-5.
Related Code Sections
308A.1.1.1.6 Provisions for All Compliance Methods, Buildings Removed From Hospital Service
The means of egress for acute care hospitals shall be permitted to pass through buildings that are removed from hospital service only ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 308A Compliance Alternatives for Means of Egress > 308A.1 General > 308A.1.1 Means of Egress > 308A.1.1.1 Means of Egress for Hospital Buildings > 308A.1.1.1.6 Buildings Removed From Hospital Service
3417A.1.1.1.6 Existing Structures, Buildings Removed From Hospital Service
The means of egress for acute care hospitals shall be permitted to pass through buildings that are removed from hospital service only ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3417A Compliance Alternatives for Means of Egress > 3417A.1 General > 3417A.1.1 Means of Egress > 3417A.1.1.1 Means of Egress for Hospital Buildings > 3417A.1.1.1.6 Buildings Removed From Hospital Service
3416A.1.1.1.5 Existing Structures, Buildings Removed From Acute-Care Hospital Service
removed from acute care hospital service until January 1, 2030 if the building removed from service meets the performance requirements of Section 3416A ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3416A Compliance Alternatives for Services/Systems and Utilities > 3416A.1 General > 3416A.1.1 Services/Systems and Utilities > 3416A.1.1.1 Services/Systems and Utilities for Hospital Buildings > 3416A.1.1.1.5 Buildings Removed From Acute-Care Hospital Service
307A.1.1.1.5 Provisions for All Compliance Methods, Buildings Removed From Acute-Care Hospital Service
removed from acute care hospital service until January 1, 2030, if the building removed from service meets the performance requirements of Section 307A ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 307A Compliance Alternatives for Services/Systems and Utilities > 307A.1 General > 307A.1.1 Services/Systems and Utilities > 307A.1.1.1 Services/Systems and Utilities for Hospital Buildings > 307A.1.1.1.5 Buildings Removed From Acute-Care Hospital Service
3418A.3 Existing Structures, Establishing Eligibility for Removal From General Acute Care Service
In order to establish that one or more SPC buildings are eligible for removal from general acute care service, the hospital owner shall submit ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3418A Removal of Hospital Buildings From General Acute Care Services > 3418A.3 Establishing Eligibility for Removal From General Acute Care Service