903.2.11.3 Buildings More Than 30 Feet (9144 MM) in Height
JUMP TO FULL CODE CHAPTER
An automatic sprinkler system shall be
installed throughout a building that has a floor level
which has an occupant load of 30 or more occupants
and which is located 30 feet (9144 mm) or more above
the lowest level of fire department vehicle access.
Exceptions:
R408.30445- Open parking structures.
- Occupancies in group F-2.
- Existing buildings having occupied floor levels
not more than 55 feet (16764 mm) in
height above the lowest level of fire department
vehicle access, where the local unit of
government complies with the following
parameters:
- The local unit of government having a municipal fire department with an ISO rating of 3 or lower, employing a fulltime career fire fighting staff.
- The governing body of the local unit of government has passed a resolution affirming the use of this exception and filed that resolution with the department of licensing and regulatory affairs, bureau of construction codes.
Related Code Sections
903.2.11.3 Fire Protection Systems, Buildings More Than 30 Feet (9144 MM) in Height
Occupancies in group F-2.
Existing buildings having occupied floor levels
not more than 55 feet (16764 mm) in
height above the lowest level ...
2015 Michigan Building Code > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.2 Where Required > 903.2.11 Specific Building Areas and Hazards > 903.2.11.3 Buildings More Than 30 Feet (9144 MM) in Height
426.1.6 Special Detailed Requirements Based on Use and Occupancy, Coal Pockets
Type IB construction. Where more than 30 feet (9144 mm) from interior lot lines , or where erected along a railroad right-of-way, the minimum type ...
2015 Michigan Building Code > 4 Special Detailed Requirements Based on Use and Occupancy > 426 Combustible Dusts, Grain Processing and Storage > 426.1 Combustible Dusts, Grain Processing and Storage > 426.1.6 Coal Pockets
406.5.5 Special Detailed Requirements Based on Use and Occupancy, Area and Height Increases
In addition, each such opening shall face a street or yard accessible to a street with a width of not less than 30 feet (9144 mm) for the full ...
2015 Michigan Building Code > 4 Special Detailed Requirements Based on Use and Occupancy > 406 Motor-Vehicle-Related Occupancies > 406.5 Open Parking Garages > 406.5.5 Area and Height Increases
905.3.1 Fire Protection Systems, Height
Class III standpipe systems shall be
installed throughout buildings where the floor level of the
highest story is located more than 30 feet (9144 ...
2015 Michigan Building Code > 9 Fire Protection Systems > 905 Standpipe Systems > 905.3 Required Installations > 905.3.1 Height
506.3.2 General Building Heights and Areas, Minimum Frontage Distance
Where the value of W is greater than 30 feet (9144 mm),
a value of 30 feet (9144 mm) shall be used in calculating
the building area increase based ...
2015 Michigan Building Code > 5 General Building Heights and Areas > 506 Building Area > 506.3 Frontage Increase > 506.3.2 Minimum Frontage Distance