Automatic and manual operation of the smoke control system may alternately be done through a Building Management System (BMS) that is approved by the Fire Department and meets the following requirements:
  1. The BMS system shall be listed for UL 864 UUKL Smoke Control.
  2. The BMS Control Center shall be staffed 24 hours a day by operators trained in the building's smoke control systems and their operation. The smoke control system shall be operated by a certificate of fitness holder where required by the New York City Fire Code.
  3. The control room shall be 2-hour fire-resistance-rated construction.
  4. BMS annunciation and additional control station locations shall be located in the fire command center in accordance with Section 909.16.

Related Code Sections

909.12.3.1 Fire Protection Systems, Building Management System
Automatic and manual operation of the smoke control system may alternately be done through a Building Management System (BMS) that meets ...
909.12.4.1 Fire Protection Systems, Building Management System
Automatic and manual operation of the smoke control system may alternately be done through a Building Management System (BMS) that is approved ...
§28-308.2 Maintenance of Buildings, Energy Audits Required
, or (ii) the building has a central heating system controlled by an energy management system or a building management system that incorporates temperature ...
§28-308.2 Maintenance of Buildings, Energy Audits Required
, or (ii) the building has a central heating system controlled by an energy management system or a building management system that incorporates temperature ...
*§28-308.2 Maintenance of Buildings, Energy Audits Required
the space, or (ii) the building has a central heating system controlled by an energy management system or a building management system that incorporates ...