// CODE SNIPPET
909.12.3.1 Building Management System
JUMP TO FULL CODE CHAPTER
Automatic and manual operation of the smoke control system may alternately be done through a Building Management System (BMS) that meets the following requirements and is approved by the Fire Department:
- The BMS system shall be listed for UL 864 UUKL Smoke Control.
- The BMS Control Center shall be staffed 24 hours a day by operators trained in the building's smoke control systems and their operation. In buildings where Fire Safety Directors are required, they shall operate the smoke control system.
- The control room shall be 2-hour rated construction.
- BMS annunciation and additional control station locations shall be located in the fire command center in accordance with Section 909.16.
Related Code Sections
909.12.3.1 Fire Protection Systems, Building Management System
Automatic and manual operation of the smoke control system may alternately be done through a Building Management System (BMS) that meets ...
NYC Building Code 2014 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.12 Detection and Control Systems > 909.12.3 Automatic Control > 909.12.3.1 Building Management System
§28-308.2 Maintenance of Buildings, Energy Audits Required
, or (ii) the building has a central heating system controlled by an energy management system or a building management system that incorporates ...
NYC General Admin. Provisions 2014 > 3 Maintenance of Buildings > 308 Energy Audits and Retro-Commissioning of Base Building Systems > §28-308.2 Energy Audits Required
*§28-308.2 Maintenance of Buildings, Energy Audits Required
the space, or (ii) the building has a central heating system controlled by an energy management system or a building management system that incorporates ...
NYC General Admin. Provisions 2008 > 3 Maintenance of Buildings > 308 *Energy Audits and Retro-Commissioning of Base Building Systems > *§28-308.2 Energy Audits Required
Article 308 Maintenance of Buildings, Energy Audits and Retro-Commissioning of Base Building Systems
BUILDING MANAGEMENT SYSTEM. A computer-based system that monitors and controls a building's mechanical and electrical equipment ...
NYC General Admin. Provisions 2014 > 3 Maintenance of Buildings > 308 Energy Audits and Retro-Commissioning of Base Building Systems
Article 308 Maintenance of Buildings, *Energy Audits and Retro-Commissioning of Base Building Systems
serves such leased space. 2. Industrial processes that occur within a covered building. BUILDING MANAGEMENT SYSTEM. A ...
NYC General Admin. Provisions 2008 > 3 Maintenance of Buildings > 308 *Energy Audits and Retro-Commissioning of Base Building Systems