**§28-320.3.2 Building Emissions Limits for Calendar Years 2030 Through 2034
JUMP TO FULL CODE CHAPTER
For calendar years 2030 through 2034 the annual building emissions limits for covered buildings shall be calculated pursuant to items 1 through 10 of this section. For the purposes of such calculation the department shall provide a method for converting categories of uses under the United States environmental protection agency Portfolio Manager tool to the equivalent uses and occupancy groups set forth in this section. For a covered building with spaces classified in more than one occupancy group, the annual building emissions limit shall be the sum of the calculated values from items 1 through 10 of this paragraph, as applicable for each space. The department may establish different limits, including a different metric or method of calculation, set forth in the rules of the department, where the department determines that different limits are feasible and in the public interest. Where such limits are set by rule, the average emission limits for all covered buildings shall not be less restrictive than the average emissions impact of the building emissions limits outlined in items 1 through 10 of this section. The advisory board and the office of long term planning and sustainability shall provide advice and recommendation regarding such limits.
**Section 28-320.3.2 was amended by: Local Law 147 of 2019. This law has an effective date of November 15, 2019.
- For spaces classified as occupancy group A: multiply the building emissions intensity limit of 0.00420 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy group B other than as described in item 6: multiply the building emissions intensity limit of 0.00453 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy groups E and I-4: multiply the building emissions intensity limit of 0.00344 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy group I-1: multiply the building emissions intensity limit of 0.00598 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy group F: multiply the building emissions intensity limit of 0.00167 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy groups B civic administrative facility for emergency response services, B non-production laboratory, Group B ambulatory health care facility, H, I-2 or I-3: multiply the building emissions intensity limit of 0.01330 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy group M: multiply the building emissions intensity limit of 0.00403 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy group R-1: multiply the building emissions intensity limit of 0.00526 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy groups R-2: multiply the building emissions intensity limit of 0.00407 tCO2e/sf by the corresponding gross floor area (sf);
- For spaces classified as occupancy groups S and U: multiply the building emissions intensity limit of 0.00110 tCO2e/sf by the corresponding gross floor area (sf).
**Section 28-320.3.2 was amended by: Local Law 147 of 2019. This law has an effective date of November 15, 2019.
For the purposes of calculating the annual building emissions of a covered building in accordance with this section, the amount of greenhouse gas emissions attributed to particular energy sources shall be determined by the commissioner and promulgated into rules of the department by no later than January 1, 2023. The commissioner shall consult with the advisory board required by this article to develop such greenhouse gas coefficients for utility electricity consumption. When developing such coefficient, the commissioner shall consider factors, including but not limited to the best available New York state energy research and development authority and State Energy Plan forecasts for Zone J for the end of the compliance period and beneficial electrification.
*Section 28-320.3.2.1 was added by: Local Law 97 of 2019. This law has an effective date of November 15, 2019.
**Section 28-320.3.2.1 was amended by: Local Law 147 of 2019. This law has an effective date of November 15, 2019.
*Section 28-320.3.2.1 was added by: Local Law 97 of 2019. This law has an effective date of November 15, 2019.
**Section 28-320.3.2.1 was amended by: Local Law 147 of 2019. This law has an effective date of November 15, 2019.
Related Code Sections
**§28-320.3.2.1 Maintenance of Buildings, Greenhouse Gas Coefficients of Energy Consumption for Calendar Years 2030 Through 2034
For the purposes of calculating the annual building emissions of a covered building in accordance with this section, the amount of greenhouse gas ...
NYC General Admin. Provisions 2014 > 3 Maintenance of Buildings > *320 Building Energy and Emissions Limits > *§28-320.3 Building Emissions Limits > **§28-320.3.2 Building Emissions Limits for Calendar Years 2030 Through 2034 > **§28-320.3.2.1 Greenhouse Gas Coefficients of Energy Consumption for Calendar Years 2030 Through 2034
*§28-320.8.1 Maintenance of Buildings, Effective Period
limit for calendar years 2030-2035, as prescribed by section 28-320.3.8. Such extension may be granted upon submission of a schedule ...
NYC General Admin. Provisions 2014 > 3 Maintenance of Buildings > *320 Building Energy and Emissions Limits > **§28-320.8 Adjustment to Applicable Annual Building Emissions Limit for Calendar Years 2024-2029 > *§28-320.8.1 Effective Period
*§28-320.8.1.1 Maintenance of Buildings, Extension of Effective Period
limit for calendar years 2030-2035, as prescribed by section 28-320.3.8. Such extension may be granted upon submission of a schedule of alterations ...
NYC General Admin. Provisions 2014 > 3 Maintenance of Buildings > *320 Building Energy and Emissions Limits > **§28-320.8 Adjustment to Applicable Annual Building Emissions Limit for Calendar Years 2024-2029 > *§28-320.8.1 Effective Period > *§28-320.8.1.1 Extension of Effective Period
*§28-320.3.4 Maintenance of Buildings, Building Emissions Limits for Calendar Years 2035 Through 2050
limits applicable for calendar years 2035 through 2039 and building emissions limits and building emissions intensity limits applicable ...
NYC General Admin. Provisions 2014 > 3 Maintenance of Buildings > *320 Building Energy and Emissions Limits > *§28-320.3 Building Emissions Limits > *§28-320.3.4 Building Emissions Limits for Calendar Years 2035 Through 2050
**§28-320.3.6.2 Maintenance of Buildings, Deductions From Reported Annual Building Emissions for Purchased Greenhouse Gas Offsets
For calendar years 2024 through 2029, a deduction shall be authorized for up to 10 percent of the annual building emissions limit. Such a deduction ...
NYC General Admin. Provisions 2014 > 3 Maintenance of Buildings > *320 Building Energy and Emissions Limits > *§28-320.3 Building Emissions Limits > **§28-320.3.6 Deductions From Reported Annual Building Emissions > **§28-320.3.6.2 Deductions From Reported Annual Building Emissions for Purchased Greenhouse Gas Offsets