P3007.2 Building Drains Below Sewer (Building Subdrains)
JUMP TO FULL CODE CHAPTER
Building drains which cannot be discharged to the sewer by gravity flow shall be discharged into a tightly covered and vented sump from which the contents shall be lifted and discharged into the building gravity drainage system by automatic pumping equipment.
The system of drainage piping below the sewer level shall be installed and vented in a manner similar to that of the gravity system. Only such drains that must be lifted for discharge shall be discharged into sumps. All other drains shall be discharged by gravity.
Exception:
Macerating toilet systems shall be permitted as an alternate to the sewage pump or ejector system. The macerating toilet shall comply with ASME A 112.3.4 or CSA B 45.9 and shall be installed in accordance with the manufacturers' instructions.
Related Code Sections
P3007.2 Sanitary Drainage, Building Drains Below Sewer (Building Subdrains)
Building drains which cannot be discharged to the sewer by gravity flow shall be discharged into a tightly covered and vented sump from which ...
2010 Residential Code of NY > 30 Sanitary Drainage > P3007 Sumps and Ejectors > P3007.2 Building Drains Below Sewer (Building Subdrains)
Section 1112 Storm Drainage, Building Subdrains
Building subdrains located below the public sewer level shall discharge into a sump or receiving tank, the contents of which shall ...
Section 1112 Storm Drainage, Building Subdrains
Building subdrains located below the public sewer level shall discharge into a sump or receiving tank, the contents of which shall be automatically ...
Section 1112 Storm Drainage, Building Subdrains
Building subdrains located below the public sewer level shall discharge into a sump or receiving tank, the contents of which shall ...
712.1 Sanitary Drainage, Building Subdrains
Building subdrains that cannot be discharged to the sewer by gravity flow shall be discharged into a tightly covered and vented sump from which ...
Plumbing Code 2015 of New York State > 7 Sanitary Drainage > 712 Sumps and Ejectors > 712.1 Building Subdrains