• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects General Contractor Building Official & Plans Examiner Inspectors Owner Subcontractors Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

1616.5.1 Building Configuration (For Use in the Simplifiedanalysis Procedure of Section 1617.5)

NYC Building Code 2008 > 16 Structural Design > 1616 Earthquake Loads — Criteria Selection > 1616.5 Building Configuration > 1616.5.1 Building Configuration (For Use in the Simplifiedanalysis Procedure of Section 1617.5)
JUMP TO FULL CODE CHAPTER
Buildings designed using the simplified analysis procedure in Section 1617.5 shall be classified as regular or irregular based on the criteria in this section. Such classification shall be based on the plan and vertical configuration. Buildings shall not exceed the limitations of Section 1616.6.1.

1616.5.1.1 Plan Irregularity

Buildings having one or more of the features listed in Table 1616.5.1.1 shall be designated as having plan structural irregularity and shall comply with the requirements in the sections referenced in that table.

TABLE 1616.5.1.1
PLAN STRUCTURAL IRREGULARITIES
IRREGULARITY TYPE AND DESCRIPTION REFERENCE
SECTION
SEISMIC DESIGN
CATEGORYa
APPLICATION
1a Torsional Irregularity - to be considered when diaphragms are not flexible as determined in section 1602.1.1

Torsional irregularity shall be considered to exist when the maximum story drift, computed including accidental torsion at one end of the structure transverse to an axis is more than 1.2 times average of the story drifts at the two ends of the structure.
9.5.5.5.2 of ASCE 7
1620.4.1
9.5.2.1 of ASCE 7
9.5.5.7.1 of ASCE 7
C and D,
D,
D,
C and D
1b
Extreme Torsional Irregularity — to be considered when diaphragms are not flexible as determined in Section 1602.1.

Extreme torsional irregularity shall be considered to exist when the maximum story drift.
9.5.5.5.2 of ASCE 7
1620.4.1
9.5.5.5.1 of ASCE 7
9.5.5.7.1 of ASCE 7
C and D,
D,
D,
C and D
2 Reentrant Corners
Plan, configurations of a structure and its lateral-force-resisting system contain reentrant corners where both projections of the structure beyond a reentrant corner are greater than 15 percent of the plan dimension of the structure in the given direction.
1620.4.1 D
3 Diaphragm Discontinuity
Diaphragms with abrupt discontinuities or variations in stiffness including those having cutout or open areas greater than 50 percent of the gross enclosed diaphragm area or changes in effective diaphragm stiffness of more than 50 percent from one story to the next.
1620.4.1 D
4 Out-of-Plane Offsets
Discontinuities in a lateral-force-resistance path, such as out-of-plane offsets of the vertical elements.
1620.4.1
9.5.2.5.1 of ASCE 7
1620.2.9
D,
D,
B, C and D
5 Nonparallel Systems
The vertical lateral-force-resisting elements are not parallel to or symmetric about the major orthogonal axes of the lateral-force-resisting system.
1620.3.2 C and D
  1. Seismic design category is determined in accordance with Section 1616.

1616.5.1.2 Vertical Irregularity

Buildings having one or more of the features listed in Table 1616.5.1.2 shall be designated as having vertical irregularity and shall comply with the requirements in the sections referenced in that table.

Exceptions:

  1. Structural irregularities of Type 1a, 1b or 2 in Table 1616.5.1.2 do not apply where no story drift ratio under design lateral load is greater than 130 percent of the story drift ratio of the next story above. Torsional effects need not be considered in the calculation of story drifts for the purpose of this determination. The story drift ratio relationship for the top two stories of the building is not required to be evaluated.
  2. Irregularities of Types 1a, 1b and 2 of Table 1616.5.1.2 are not required to be considered for one-story buildings in any seismic design category or for two-story buildings in Seismic Design Category B, C or D.

TABLE 1616.5.1.2
VERTICAL STRUCTURAL IRREGULARITIES
IRREGULARITY TYPE AND DESCRIPTION REFERENCE
SECTION
SEISMIC DESIGN
CATEGORYa
APPLICATION
1a Stiffness Irregularity—Soft Story

A soft story is one in which the lateral stiffness is less than 70 percent of that in the story above or less than 80 percent of the average stiffness of the three stories above.
9.5.2.5.1 of ASCE 7 D
1b Stiffness Irregularity—Extreme Soft Story

An extreme soft story is one in which the lateral stiffness is less than 60 percent of that in the story above or less than 70 percent of the average stiffness of the three stories above
9.5.2.5.1 of ASCE 7 D
2 Weight (Mass) Irregularity

Mass irregularity shall be considered to exist where the effective mass of any story is more than 150 percent of the effective mass of an adjacent story. A roof that is lighter than the floor below need not be considered.
9.5.2.5.1 of ASCE 7 D
3 Vertical Geometric Irregularity

Vertical geometric irregularity shall be considered to exist where the horizontal dimension of the lateral-force-resisting system in any story is more than 130 percent of than in an adjacent story.
9.5.2.5.1 of ASCE 7 D, E and F
4 In-plane Discontinuity in Vertical Lateral-Force-Resisting Elements

An in-plane offset of the lateral-force-resisting elements greater than the length of those elements or a reduction in stiffness of the resisting element in the story below.
1620.4.1
9.5.2.5.1 of ASCE 7
1620.2.9
D,
D,
B, C and D
5 Discontinuity in Capacity—Weak Story

A weak story is one in which the story lateral strength is less than 80 percent of that in the story above.The story strength is the total strength of seismic-resisting elements sharing the story shear for the direction under consideration.
1620.2.3
9.5.2.5.1 of ASCE 7
B, C and D,
D
  1. Seismic design category is determined in accordance with Section 1616.

Related Code Sections


1616.5.1 Structural Design, Building Configuration (For Use in the Simplifiedanalysis Procedure of Section 1617.5)
Buildings designed using the simplified analysis procedure in Section 1617.5 shall be classified as regular or irregular based on the criteria ...
NYC Building Code 2008 > 16 Structural Design > 1616 Earthquake Loads — Criteria Selection > 1616.5 Building Configuration > 1616.5.1 Building Configuration (For Use in the Simplifiedanalysis Procedure of Section 1617.5)
1617.5 Structural Design, Simplified Analysis Procedure for Seismic Design of Buildings
See Section 1616.6.1 for limitations on the use of this procedure. For purposes of this analytical procedure, a building is considered to be fixed ...
NYC Building Code 2008 > 16 Structural Design > 1617 Earthquake Loads — Minimum Designlateral Force and Related Effects > 1617.5 Simplified Analysis Procedure for Seismic Design of Buildings
1617.5 Structural Design, Extent of the Structural Peer Review
components (such as certain precast concrete elements) have been appropriately specified and coordinated with the primary building structure. Verify ...
NYC Building Code 2014 > 16 Structural Design > 1617 Structural Peer Review > 1617.5 Extent of the Structural Peer Review
1616.6.1 Structural Design, Simplified Analysis
A simplified analysis, in accordance with Section 1617.5, shall be permitted to be used for any structure in Seismic Use Group I, subject ...
NYC Building Code 2008 > 16 Structural Design > 1616 Earthquake Loads — Criteria Selection > 1616.6 Analysis Procedures > 1616.6.1 Simplified Analysis
1617.3.1 Structural Design, Deflection and Drift Limits (For Use in the Simplified Analysis Procedure of Section 1617.5)
the limitations of Section 1616.6.1. TABLE 1617.3.1 ALLOWABLE STORY DRIFT, Δ a a BUILDING SEISMIC USE GROUP ...
NYC Building Code 2008 > 16 Structural Design > 1617 Earthquake Loads — Minimum Designlateral Force and Related Effects > 1617.3 Deflection and Drift Limits > 1617.3.1 Deflection and Drift Limits (For Use in the Simplified Analysis Procedure of Section 1617.5)
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL LEARN MORE