Listed, hard usage (junior hard service) cords shall be permitted in breakout assemblies where all of the following conditions are met:
  1. The cords are utilized to connect between a single multi-pole connector containing two or more branch circuits and multiple 2-pole, 3-wire connectors.
  2. The longest cord in the breakout assembly does not exceed 6.0 m (20 ft).
  3. The breakout assembly is protected from physical damage by attachment over its entire length to a pipe, truss, tower, scaffold, or other substantial support structure.
  4. All branch circuits feeding the breakout assembly are protected by overcurrent devices rated at not over 20 amperes.