E3702.7 Branch Circuits Serving Motor-Operated and Combination Loads
JUMP TO FULL CODE CHAPTER
For circuits supplying loads consisting
of motor-operated utilization equipment that is fastened in
place and that has a motor larger than 1/8 horsepower (0.093
kW) in combination with other loads, the total calculated load
shall be based on 125 percent of the largest motor load plus
the sum of the other loads. [220.18(A)]
Related Code Sections
E3702.7 Branch Circuit and Feeder Requirements, Branch Circuits Serving Motor-Operated and Combination Loads
For circuits supplying loads consisting
of motor-operated utilization equipment that is fastened in
place and that has a motor larger than 1 / 8 ...
2015 Michigan Residential Code > 37 Branch Circuit and Feeder Requirements > E3702 Branch Circuit Ratings > E3702.7 Branch Circuits Serving Motor-Operated and Combination Loads
Section E3703 Branch Circuit and Feeder Requirements, Required Branch Circuits
, up to and including
the branch-circuit panelboard(s), shall have the capacity to
serve not less than the calculated load. This load shall be
evenly ...
2015 Michigan Residential Code > 37 Branch Circuit and Feeder Requirements > E3703 Required Branch Circuits
E3701.2 Branch Circuit and Feeder Requirements, Branch-Circuit and Feeder Ampacity
Branch-circuit
and feeder conductors shall have ampacities not less than
the maximum load to be served. Where a branch circuit or a
feeder supplies ...
2015 Michigan Residential Code > 37 Branch Circuit and Feeder Requirements > E3701 General > E3701.2 Branch-Circuit and Feeder Ampacity
E4101.5 Appliance Installation, Disconnecting Means
horsepower, the branch circuit switch or circuit breaker shall be permitted to serve as the disconnecting means where the switch or circuit breaker ...
2015 Michigan Residential Code > 41 Appliance Installation > E4101 General > E4101.5 Disconnecting Means
E3703.5 Branch Circuit and Feeder Requirements, Number of Branch Circuits
The minimum number
of branch circuits shall be determined from the total calculated
load and the size or rating of the circuits used. The number ...
2015 Michigan Residential Code > 37 Branch Circuit and Feeder Requirements > E3703 Required Branch Circuits > E3703.5 Number of Branch Circuits