R602.10.5.3 Braced Wall Panel Location and Corner Construction
JUMP TO FULL CODE CHAPTER
A braced wall panel shall be located at each end of a continuously-sheathed braced wall line. A minimum 32-inch (813 mm) structural fiberboard sheathing panel corner return shall be provided at both ends of a continuously-sheathed braced wall line in accordance with Figure R602.10.4.4(1) In lieu of the corner return, a hold-down device with a minimum uplift design value of 800 pounds (3560 N) shall be fastened to the corner stud and to the foundation or framing below in accordance with Figure R602.10.4.4(3).
Exception: The first braced wall panel shall be permitted to begin 12 feet 6 inches (3810 mm) from each end of the braced wall line in Seismic Design Categories A, B and C provided one of the following is satisfied:
- A minimum 32-inch-long (813 mm), full-height structural fiberboard sheathing panel is provided at both sides of a corner constructed in accordance with Figure R602.10.4.4(1) at the braced wall line ends in accordance with Figure R602.10.4.4(4), or
- The braced wall panel closest to the corner shall have a hold-down device with a minimum uplift design value of 800 pounds (3560 N) fastened to the stud at the edge of the braced wall panel closest to the corner and to the foundation or framing below in accordance with Figure R602.10.4.4(5).
Related Code Sections
R602.10.5.3 Wall Construction, Braced Wall Panel Location and Corner Construction
A braced wall panel shall be located at each end of a continuously-sheathed braced wall line . A minimum 32-inch (813 mm) structural fiberboard ...
Residential Code 2009 of Tennessee > 6 Wall Construction > R602 Wood Wall Framing > R602.10 Wall Bracing > R602.10.5 Continuously-Sheathed Braced Wall Line Using Method CS-SFB (Structural Fiberboard Sheathing) > R602.10.5.3 Braced Wall Panel Location and Corner Construction
R613.5.3 Wall Construction, Wall Bracing
SIP walls shall be braced in accordance with Section R602.10. SIP walls shall be considered continuous wood structural panel sheathing for purposes ...
Residential Code 2009 of Tennessee > 6 Wall Construction > R613 Structural Insulated Panel Wall Construction > R613.5 Wall Construction > R613.5.3 Wall Bracing
R602.10.1 Wall Construction, Braced Wall Lines
a braced wall panel located at each end of the braced wall line .
Exception:
For braced wall panel construction Method WSP of Section R602.10.2 ...
Residential Code 2009 of Tennessee > 6 Wall Construction > R602 Wood Wall Framing > R602.10 Wall Bracing > R602.10.1 Braced Wall Lines
R602.10.4 Wall Construction, Continuous Sheathing
of a braced wall line including areas above and below openings and gable end walls. Braced wall panels shall be constructed in accordance with one ...
Residential Code 2009 of Tennessee > 6 Wall Construction > R602 Wood Wall Framing > R602.10 Wall Bracing > R602.10.4 Continuous Sheathing
R602.10.1.3 Wall Construction, Angled Corners
At corners, braced wall line s shall be permitted to angle out of plane up to 45 degrees with a maximum diagonal length of 8 feet (2438 mm). When ...
Residential Code 2009 of Tennessee > 6 Wall Construction > R602 Wood Wall Framing > R602.10 Wall Bracing > R602.10.1 Braced Wall Lines > R602.10.1.3 Angled Corners