2308.3.2 Braced Wall Line Connections
JUMP TO FULL CODE CHAPTER
Wind and seismic lateral forces shall be transferred from the roof and floor diaphragms to braced wall lines and from the braced wall lines in upper stories to the braced wall lines in the story below in accordance with Sections 2308.3.2.1 and 2308.3.2.2.
Braced wall line bottom plates shall be connected to joists or full-depth blocking below in accordance with Table 2304.9.1, Item 6, or to foundations in accordance with Section 2308.3.3.
Where joists and/or rafters are used, braced wall line top plates shall be fastened over the full length of the braced wall line to joists, rafters, rimboards or blocking above in accordance with Table 2304.9.1, Items 11, 12, 15 or 19, as applicable, based on the orientation of the joists or rafters to the braced wall line. Blocking at joists with walls above shall be equal to the depth of the joist at the braced wall line. Blocking at rafters need not be full depth but shall extend to within 2 inches (51 mm) from the roof sheathing above. Blocking shall be a minimum of 2 inches (51 mm) nominal thickness and shall be fastened to the braced wall line top plate as specified in Table 2304.9.1, Item 11. Notching or drilling of holes in blocking in accordance with the requirements of Section 2308.8.2 or Section 2308.10.4.2 shall be permitted.
At exterior gable end walls braced wall panel sheathing in the top story shall be extended and fastened to roof framing where the spacing between parallel exterior braced wall lines is greater than 50 feet (15 240 mm).
Where roof trusses are used and are installed perpendicular to an exterior braced wall line, lateral forces shall be transferred from the roof diaphragm to the braced wall over the full length of the braced wall line by blocking of the ends of the trusses or by other approved methods providing equivalent lateral force transfer. Blocking shall be minimum 2 inches (51 mm) nominal thickness and shall extend to within 2 inches (51 mm) from the roof sheathing above and shall be fastened to the braced wall line top plate as specified in Table 2304.9.1, Item 11. Notching or drilling of holes in blocking in accordance with the requirements of Section 2308.8.2 or Section 2308.10.4.2 shall be permitted.
At exterior gable end walls braced wall panel sheathing in the top story shall be extended and fastened to roof framing where the spacing between parallel exterior braced wall lines is greater than 50 feet (15 240 mm).
Where roof trusses are used and are installed perpendicular to an exterior braced wall line, lateral forces shall be transferred from the roof diaphragm to the braced wall over the full length of the braced wall line by blocking of the ends of the trusses or by other approved methods providing equivalent lateral force transfer. Blocking shall be minimum 2 inches (51 mm) nominal thickness and shall extend to within 2 inches (51 mm) from the roof sheathing above and shall be fastened to the braced wall line top plate as specified in Table 2304.9.1, Item 11. Notching or drilling of holes in blocking in accordance with the requirements of Section 2308.8.2 or Section 2308.10.4.2 shall be permitted.
Related Code Sections
2308.3.2 Wood, Braced Wall Line Connections
Braced wall line bottom plates shall be connected to joists or full-depth blocking below ...
Building Code 2012 of South Holland, IL > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.3 Braced Wall Lines > 2308.3.2 Braced Wall Line Connections
2308.11 Wood, Additional Requirements for Conventional Construction in Seismic Design Category B or C
25 percent of the braced wall line length. Braced wall panels in the first story shall be located in accordance with Section 2308.9.3 and not more ...
Building Code 2012 of South Holland, IL > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.11 Additional Requirements for Conventional Construction in Seismic Design Category B or C
2308.11.2 Wood, Concrete or Masonry
panels shall be not less than 25 percent of the braced wall line length. Braced wall panels in the first story shall be located in accordance ...
Building Code 2012 of South Holland, IL > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.11 Additional Requirements for Conventional Construction in Seismic Design Category B or C > 2308.11.2 Concrete or Masonry
2308.3.3.1 Wood, Anchorage to All-Wood Foundations
Where all-wood foundations are used, the force transfer from the braced wall lines shall be determined based on calculation and shall have a capacity ...
Building Code 2012 of South Holland, IL > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.3 Braced Wall Lines > 2308.3.3 Sill Anchorage > 2308.3.3.1 Anchorage to All-Wood Foundations
2308.12 Wood, Additional Requirements for Conventional Construction in Seismic Design Category D or E
Figure 2308.12.6(4)] provided that the framing members are connected to the braced wall line below in accordance with Section 2308.3.2.
Where ...
Building Code 2012 of South Holland, IL > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.12 Additional Requirements for Conventional Construction in Seismic Design Category D or E