• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section E3905 Boxes, Conduit Bodies and Fittings

Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3905 Boxes, Conduit Bodies and Fittings
JUMP TO FULL CODE CHAPTER

E3905.1 Box, Conduit Body or Fitting—Where Required

A box or conduit body shall be installed at each conductor splice point, outlet, switch point, junction point and pull point except as otherwise permitted in Sections E3905.1.1 through E3905.1.6.
Fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed. (300.15)

E3905.1.1 Equipment

An integral junction box or wiring compartment that is part of listed equipment shall be permitted to serve as a box or conduit body. [300.15(B)]

E3905.1.2 Protection

A box or conduit body shall not be required where cables enter or exit from conduit or tubing that is used to provide cable support or protection against physical damage. A fitting shall be provided on the end(s) of the conduit or tubing to protect the cable from abrasion. [300.15(C)]

E3905.1.3 Integral Enclosure

A wiring device with integral enclosure identified for the use, having brackets that securely fasten the device to walls or ceilings of conventional on-site frame construction, for use with nonmetallic-sheathed cable, shall be permitted in lieu of a box or conduit body. [300.15(E)]

E3905.1.4 Fitting

A fitting identified for the use shall be permitted in lieu of a box or conduit body where such fitting is accessible after installation and does not contain spliced or terminated conductors. [300.15(F)]

E3905.1.5 Buried Conductors

Splices and taps in buried conductors and cables shall not be required to be enclosed in a box or conduit body where installed in accordance with Section E3803.4.

E3905.1.6 Luminaires

Where a luminaire is listed to be used as a raceway, a box or conduit body shall not be required for wiring installed therein. [300.15(J)]

E3905.2 Metal Boxes

Metal boxes shall be grounded. (314.4)

E3905.3 Nonmetallic Boxes

Nonmetallic boxes shall be used only with cabled wiring methods with entirely nonmetallic sheaths, flexible cords and nonmetallic raceways. (314.3)
Exceptions:
  1. Where internal bonding means are provided between all entries, nonmetallic boxes shall be permitted to be used with metal raceways and metal-armored cables. (314.3 Exception No. 1)
  2. Where integral bonding means with a provision for attaching an equipment grounding jumper inside the box are provided between all threaded entries in nonmetallic boxes listed for the purpose, nonmetallic boxes shall be permitted to be used with metal raceways and metal-armored cables. (314.3 Exception No. 2)

E3905.3.1 Nonmetallic-Sheathed Cable and Nonmetallic Boxes

Where nonmetallic-sheathed cable is used, the cable assembly, including the sheath, shall extend into the box not less than 1/4 inch (6.4 mm) through a nonmetallic-sheathed cable knockout opening. (314.7(C)]

E3905.3.2 Securing to Box

Wiring methods shall be secured to the boxes. [314.17(C)]
Exception: Where nonmetallic-sheathed cable is used with boxes not larger than a nominal size of 21/4 inches by 4 inches (57 mm by 102 mm) mounted in walls or ceilings, and where the cable is fastened within 8 inches (203 mm) of the box measured along the sheath, and where the sheath extends through a cable knockout not less than 1/4 inch (6.4 mm), securing the cable to the box shall not be required. [314.17(C) Exception]

E3905.3.3 Conductor Rating

Nonmetallic boxes shall be suitable for the lowest temperature-rated conductor entering the box. [314.17(C)]

E3905.4 Minimum Depth of Boxes for Outlets, Devices, and Utilization Equipment

Outlet and device boxes shall have an approved depth to allow equipment installed within them to be mounted properly and without the likelihood of damage to conductors within the box. (314.24)

E3905.4.1 Outlet Boxes Without Enclosed Devices or Utilization Equipment

Outlet boxes that do not enclose devices or utilization equipment shall have an internal depth of not less than 1/2 inch (12.7 mm). [314.24(A)]

E3905.4.2 Utilization Equipment

Outlet and device boxes that enclose devices or utilization equipment shall have a minimum internal depth that accommodates the rearward projection of the equipment and the size of the conductors that supply the equipment. The internal depth shall include that of any extension boxes, plaster rings, or raised covers. The internal depth shall comply with all of the applicable provisions that follow. [314.24(B)]
  1. Large equipment. Boxes that enclose devices or utilization equipment that projects more than 17/8 inches (48 mm) rearward from the mounting plane of the box shall have a depth that is not less than the depth of the equipment plus 1/4 inch (6.4 mm). [314.24(B)(1)]
  2. Conductors larger than 4 AWG. Boxes that enclose devices or utilization equipment supplied by conductors larger than 4 AWG shall be identified for their specific function. [314.24(B)(2)]
  3. Conductors 8, 6, or 4 AWG. Boxes that enclose devices or utilization equipment supplied by 8, 6, or 4 AWG conductors shall have an internal depth that is not less than 21/16 inches (52.4 mm). [314.24(B)(3)]
  4. Conductors 12 or 10 AWG. Boxes that enclose devices or utilization equipment supplied by 12 or 10 AWG conductors shall have an internal depth that is not less than 13/16 inches (30.2 mm). Where the equipment projects rearward from the mounting plane of the box by more than 1 inch (25.4 mm), the box shall have a depth that is not less than that of the equipment plus 1/4 inch (6.4 mm). [314.24(B)(4)]
  5. Conductors 14 AWG and smaller. Boxes that enclose devices or utilization equipment supplied by 14 AWG or smaller conductors shall have a depth that is not less than 15/16 inch (23.8 mm). [314.24(B)(5)]
Exception: Utilization equipment that is listed to be installed with specified boxes.

E3905.5 Boxes Enclosing Flush-Mounted Devices

Boxes enclosing flush-mounted devices shall be of such design that the devices are completely enclosed at the back and all sides and shall provide support for the devices. Screws for supporting the box shall not be used for attachment of the device contained therein. (314.19)

E3905.6 Boxes at Luminaire Outlets

Outlet boxes used at luminaire or lampholder outlets shall be designed for the support of luminaires and lampholders and shall be installed as required by Section E3904.3. [314.27(A)]

E3905.6.1 Vertical Surface Outlets

Boxes used at luminaire or lampholder outlets in or on a vertical surface shall be identified and marked on the interior of the box to indicate the maximum weight of the luminaire or lamp holder that is permitted to be supported by the box if other than 50 pounds (22.7 kg). [314.27(A)(1)]
Exception: A vertically mounted luminaire or lampholder weighing not more than 6 pounds (2.7 kg) shall be permitted to be supported on other boxes or plaster rings that are secured to other boxes, provided that the luminaire or its supporting yoke is secured to the box with not fewer than two No. 6 or larger screws. [314.27(A)(1) Exception]

E3905.6.2 Ceiling Outlets

For outlets used exclusively for lighting, the box shall be designed or installed so that a luminaire or lampholder can be attached. Such boxes shall be capable of supporting a luminaire weighing up to 50 pounds (22.7 kg). A luminaire that weighs more than 50 pounds (22.7 kg) shall be supported independently of the outlet box, unless the outlet box is listed for not less than the weight to be supported. The interior of the box shall be marked by the manufacturer to indicate the maximum weight that the box is permitted to support. [314.27(A)(2)]

E3905.7 Floor Boxes

Where outlet boxes for receptacles are installed in the floor, such boxes shall be listed specifically for that application. [314.27(B)]

E3905.8 Boxes at Fan Outlets

Outlet boxes and outlet box systems used as the sole support of ceiling-suspended fans (paddle) shall be marked by their manufacturer as suitable for this purpose and shall not support ceiling-suspended fans (paddle) that weigh more than 70 pounds (31.8 kg). For outlet boxes and outlet box systems designed to support ceiling-suspended fans (paddle) that weigh more than 35 pounds (15.9 kg), the required marking shall include the maximum weight to be supported.
Where spare, separately switched, ungrounded conductors are provided to a ceiling-mounted outlet box and such box is in a location acceptable for a ceiling-suspended (paddle) fan, the outlet box or outlet box system shall be listed for sole support of a ceiling-suspended (paddle) fan. [314.27(C)]

E3905.9 Utilization Equipment

Boxes used for the support of utilization equipment other than ceiling-suspended (paddle) fans shall meet the requirements of Sections E3905.6.1 and E3905.6.2 for the support of a luminaire that is the same size and weight. [314.27(D)]
Exception: Utilization equipment weighing not more than 6 pounds (2.7 kg) shall be permitted to be supported on other boxes or plaster rings that are secured to other boxes, provided that the equipment or its supporting yoke is secured to the box with not fewer than two No. 6 or larger screws. [314.27(D) Exception]

E3905.10 Conduit Bodies and Junction, Pull and Outlet Boxes to Be Accessible

Conduit bodies and junction, pull and outlet boxes shall be installed so that the wiring therein can be accessed without removing any part of the building or structure or, in underground circuits, without excavating sidewalks, paving, earth or other substance used to establish the finished grade. (314.29)
Exception: Boxes covered by gravel, light aggregate or noncohesive granulated soil shall be listed for the application, and the box locations shall be effectively identified and access shall be provided for excavation. (314.29 Exception)

E3905.11 Damp or Wet Locations

In damp or wet locations, boxes, conduit bodies and fittings shall be placed or equipped so as to prevent moisture from entering or accumulating within the box, conduit body or fitting. Boxes, conduit bodies and fittings installed in wet locations shall be listed for use in wet locations.
Where drainage openings are installed in the field in boxes or conduit bodies listed for use in damp or wet locations, such openings shall be approved, not smaller than 1/8 inch (3 mm) and not larger than 1/4 inch (6.4 mm). For listed drain fittings, larger openings are permitted where installed in the field in accordance with the manufacturer's instructions. (314.15)

E3905.12 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies

Boxes and conduit bodies shall be of an approved size to provide free space for all enclosed conductors. In no case shall the volume of the box, as calculated in Section E3905.12.1, be less than the box fill calculation as calculated in Section E3905.12.2. The minimum volume for conduit bodies shall be as calculated in Section E3905.12.3. The provisions of this section shall not apply to terminal housings supplied with motors or generators. (314.16)

E3905.12.1 Box Volume Calculations

The volume of a wiring enclosure (box) shall be the total volume of the assembled sections, and, where used, the space provided by plaster rings, domed covers, extension rings, etc., that are marked with their volume in cubic inches or are made from boxes the dimensions of which are listed in Table E3905.12.1. Where a box is provided with one or more securely installed barriers, the volume shall be apportioned to each of the resulting spaces. Each barrier, if not marked with its volume, shall be considered to take up to 0.5 cubic inch (8.2 cm3) if metal, and 1.0 cubic inch (16.4 cm3) if nonmetallic. [314.16(A)]
TABLE E3905.12.1 [Table 314.16(A)]
MAXIMUM NUMBER OF CONDUCTORS IN METAL BOXESa
BOX DIMENSIONS
(inches trade size and type)
MAXIMUM CAPACITY
(cubic inches)
MAXIMUM NUMBER OF CONDUCTORSa
18 Awg 16 Awg 14 Awg 12 Awg 10 Awg 8 Awg 6 Awg
4 × 11/4 round or octagonal 12.5 8 7 6 5 5 4 2
4 × 11/2 round or octagonal 15.5 10 8 7 6 6 5 3
4 × 21/8 round or octagonal 21.5 14 12 10 9 8 7 4
4 × 11/4 square 18.0 12 10 9 8 7 6 3
4 × 11/2 square 21.0 14 12 10 9 8 7 4
4 × 21/8 square 30.3 20 17 15 13 12 10 6
411/16 × 11/4 square 25.5 17 14 12 11 10 8 5
411/16 × 11/2 square 29.5 19 16 14 13 11 9 5
411/16 × 21/8 square 42.0 28 24 21 18 16 14 8
3 × 2 × 11/2 device 7.5 5 4 3 3 3 2 1
3 × 2 × 2 device 10.0 6 5 5 4 4 3 2
3 × 2 × 21/4 device 10.5 7 6 5 4 4 3 2
3 × 2 × 21/2 device 12.5 8 7 6 5 5 4 2
3 × 2 × 23/4 device 14.0 9 8 7 6 5 4 2
3 × 2 × 31/2 device 18.0 12 10 9 8 7 6 3
4 × 21/8 × 11/2 device 10.3 6 5 5 4 4 3 2
4 × 21/8 × 17/8 device 13.0 8 7 6 5 5 4 2
4 × 21/8 × 21/8 device 14.5 9 8 7 6 5 4 2
33/4 × 2 × 21/2 masonry box/gang 14.0 9 8 7 6 5 4 2
33/4 × 2 × 31/2 masonry box/gang 21.0 14 12 10 9 8 7 4
For SI: 1 inch = 25.4 mm, 1 cubic inch = 16.4 cm3.
  1. Where volume allowances are not required by Sections E3905.12.2.2 through E3905.12.2.5.

E3905.12.1.1 Standard Boxes

The volumes of standard boxes that are not marked with a cubic-inch capacity shall be as given in Table E3905.12.1. [314.16(A)(1)]
SEE MORE

Related Code Sections


(A) Wiring Methods and Materials, Box, Conduit Body, or Fitting
A box, conduit body, or terminal fitting having a separately bushed hole for each conductor shall be used wherever a change is made from conduit ...
National Electrical Code 2017 of Kansas > 3 Wiring Methods and Materials > 300 General Requirements for Wiring Methods and Materials > 300.16 Raceway or Cable to Open or Concealed Wiring > (A) Box, Conduit Body, or Fitting
Section E3905 Power and Lighting Distribution, Boxes, Conduit Bodies and Fittings
of a box or conduit body where such fitting is accessible after installation and does not contain spliced or terminated conductors. [300.15(F ...
Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3905 Boxes, Conduit Bodies and Fittings
314.40 Wiring Methods and Materials, Metal Boxes, Conduit Bodies, and Fittings
Metal boxes, conduit bodies, and fittings shall be corrosion resistant or shall be well-galvanized, enameled, or otherwise properly coated inside ...
National Electrical Code 2017 of Kansas > 3 Wiring Methods and Materials > 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; And Handhole Enclosures > 314.40 Metal Boxes, Conduit Bodies, and Fittings
(C) Special Occupancies, Equipment Enclosures, Boxes, Conduit Bodies, and Fittings
Equipment enclosures, boxes, conduit bodies, and fittings installed in areas of buildings where excessive dust may be present shall be designed ...
National Electrical Code 2017 of Kansas > 5 Special Occupancies > 547 Agricultural Buildings > 547.5 Wiring Methods > (C) Equipment Enclosures, Boxes, Conduit Bodies, and Fittings
E3906.1 Power and Lighting Distribution, Conductors Entering Boxes, Conduit Bodies or Fittings
Conductors entering boxes, conduit bodies or fittings shall be protected from abrasion. (314.17 ...
Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3906 Installation of Boxes, Conduit Bodies and Fittings > E3906.1 Conductors Entering Boxes, Conduit Bodies or Fittings
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING