E3905.1 Box, Conduit Body or Fitting—Where Required
JUMP TO FULL CODE CHAPTER
A box or conduit body shall be installed at each conductor splice point, outlet, switch point, junction point and pull point except as otherwise permitted in Sections E3905.1.1 through E3905.1.6.
Fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed. (300.15)
An integral junction box or wiring compartment that is part of listed equipment shall be permitted to serve as a box or conduit body. [300.15(B)]
A box or conduit body shall not be required where cables enter or exit from conduit or tubing that is used to provide cable support or protection against physical damage. A fitting shall be provided on the end(s) of the conduit or tubing to protect the cable from abrasion. [300.15(C)]
A wiring device with integral enclosure identified for the use, having brackets that securely fasten the device to walls or ceilings of conventional on-site frame construction, for use with nonmetallic-sheathed cable, shall be permitted in lieu of a box or conduit body. [300.15(E)]
A fitting identified for the use shall be permitted in lieu of a box or conduit body where such fitting is accessible after installation and does not contain spliced or terminated conductors. [300.15(F)]
Splices and taps in buried conductors and cables shall not be required to be enclosed in a box or conduit body where installed in accordance with Section E3803.4.
Where a luminaire is listed to be used as a raceway, a box or conduit body shall not be required for wiring installed therein. [300.15(J)]
Related Code Sections
E3905.1 Power and Lighting Distribution, Box, Conduit Body or Fitting—Where Required
)] A box or conduit body shall not be required where cables enter or exit from ...
Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3905 Boxes, Conduit Bodies and Fittings > E3905.1 Box, Conduit Body or Fitting—Where Required
E3905.1.3 Power and Lighting Distribution, Integral Enclosure
on-site frame construction, for use with nonmetallic-sheathed cable, shall be permitted in lieu of a box or conduit body. [300.15(E)] ...
Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3905 Boxes, Conduit Bodies and Fittings > E3905.1 Box, Conduit Body or Fitting—Where Required > E3905.1.3 Integral Enclosure
Section E3905 Power and Lighting Distribution, Boxes, Conduit Bodies and Fittings
)] A box or conduit body shall not be required where cables enter or exit from ...
Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3905 Boxes, Conduit Bodies and Fittings
E3905.12.3 Power and Lighting Distribution, Conduit Bodies
Conduit bodies enclosing 6 AWG conductors or smaller, other than short-radius conduit bodies, shall have a cross-sectional area not less than twice ...
Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3905 Boxes, Conduit Bodies and Fittings > E3905.12 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies > E3905.12.3 Conduit Bodies
Section E3906 Power and Lighting Distribution, Installation of Boxes, Conduit Bodies and Fittings
Conductors entering boxes, conduit bodies or fittings shall be protected from abrasion. (314.17 ...
Residential Code 2018 of Kansas > 39 Power and Lighting Distribution > E3906 Installation of Boxes, Conduit Bodies and Fittings