1312.2 Bonding of CSST Gas Piping
JUMP TO FULL CODE CHAPTER
CSST gas piping
systems shall be bonded to the electrical service grounding
electrode system. The bonding jumper shall connect to a
metallic pipe or fitting between the point of delivery and the
first downstream CSST fitting. The bonding jumper shall be
not smaller than 6 AWG copper wire or equivalent. Gas
piping systems that contain one or more segments of CSST
shall be bonded in accordance with this section. [NFPA
54:7.13.2]
Related Code Sections
1211.2 Fuel Gas Piping, Bonding of CSST Gas Piping
CSST gas piping systems, and gas piping systems containing one or more segments of CSST, shall be bonded to the electrical service grounding ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1211.0 Electrical Bonding and Grounding > 1211.2 Bonding of CSST Gas Piping
1311.2 Fuel Gas Piping, Bonding of CSST Gas Piping
CSST gas piping
systems, and gas piping systems containing one or more segments
of CSST, shall be bonded to the electrical service
grounding ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1311.0 Electrical Bonding and Grounding > 1311.2 Bonding of CSST Gas Piping
1312.2 Fuel Gas Piping, Bonding of CSST Gas Piping
CSST gas piping
systems shall be bonded to the electrical service grounding
electrode system. The bonding jumper shall connect to a
metallic pipe ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1312.0 Electrical Bonding and Grounding > 1312.2 Bonding of CSST Gas Piping
1211.2.3 Fuel Gas Piping, Bonding Jumper Length
The length of the jumper between the connection to the gas piping system
and the grounding electrode system shall not exceed 75 feet (22 875 mm). Any ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1211.0 Electrical Bonding and Grounding > 1211.2 Bonding of CSST Gas Piping > 1211.2.3 Bonding Jumper Length
1211.2.5 Fuel Gas Piping, Devices Used for Bonding
Devices used for the bonding connection shall be listed for the application in accordance with UL 467. [NFPA 54:7.13.2.5] ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1211.0 Electrical Bonding and Grounding > 1211.2 Bonding of CSST Gas Piping > 1211.2.5 Devices Used for Bonding