Regardless of the voltage of the electrical system, the electrical continuity of non—current-carrying metal parts of equipment, raceways, and other enclosures in any hazardous (classified) location, as defined in 500.5, 505.5, and 506.5, shall be ensured by any of the bonding methods specified in 250.92(B)(2) through (B)(4). One or more of these bonding methods shall be used whether or not equipment grounding conductors of the wire type are installed.
Informational Note: See 501.30, 502.30, 503.30, 505.25, or 506.25 for specific bonding requirements.
Upcodes Diagrams

Related Code Sections

250.100 Wiring and Protection, Bonding in Hazardous (Classified) Locations
enclosures in any hazardous (classified) location, as defined in 500.5, 505.5, and 506.5, shall be ensured by any of the bonding methods specified ...
250.100 Wiring and Protection, Bonding in Hazardous (Classified) Locations
enclosures in any hazardous (classified) location, as defined in 500.5, 505.5, and 506.5, shall be ensured by any of the bonding methods specified ...
(A) Special Occupancies, Intrinsically Safe Apparatus
Intrinsically safe apparatus, if of metal, shall be bonded in the hazardous (classified) location in accordance with 501.30(A), 502.30(A), 503.30(A ...