(B) Bonded Neutral Generators
Go To Full Code Chapter
Bonded generators shall be provided with GFCI protection on all 125-volt, 15- and 20-ampere receptacle outlets.
Informational Note: Refer to 590.6(A)(3) for GFCI requirements for 15-kW or smaller portable generators used for temporary electric power and lighting.
Exception to (A) and (B): If the generator was manufactured or remanufactured prior to January 1, 2015, listed cord sets or devices incorporating listed GFCI protection for personnel identified for portable use shall be permitted.
Related Code Sections
(B) Equipment for General Use, Bonded Neutral Generators
Bonded generators shall be provided with GFCI protection on all 125-volt, 15- and 20-ampere receptacle outlets. Informational Note: Refer to 590.6(A ...
(B) Equipment for General Use, Bonded Neutral Generators
Bonded generators shall be provided with GFCI protection on all 125-volt, 15- and 20-ampere receptacle outlets. Informational Note: Refer to 590.6(A ...
(C) Special Conditions, Power Inlet
: WARNING: FOR CONNECTION OF A SEPARATELY DERIVED (BONDED NEUTRAL) SYSTEM ONLY or WARNING: FOR CONNECTION OF A NONSEPARATELY DERIVED (FLOATING NEUTRAL ...
(C) Special Conditions, Power Inlet
: WARNING: FOR CONNECTION OF A SEPARATELY DERIVED (BONDED NEUTRAL) SYSTEM ONLY or WARNING: FOR CONNECTION OF A NONSEPARATELY DERIVED (FLOATING NEUTRAL ...
250.36 Wiring and Protection, High-Impedance Grounded Neutral Systems
grounded system conductor from the neutral point of the transformer or generator to its connection point to the grounding impedance shall be fully ...