408.1 Approval
Bidets shall conform to ASME A112.19.2/CSA B45.1 or ASME A112.19.3/CSA B45.4.
408.2 Water Connection
The water supply to a bidet shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.14.1, 608.14.2, 608.14.3, 608.14.5608.14.6 or 608.14.8.
408.3 Bidet Water Temperature
The discharge water temperature from a bidet fitting shall be limited to not greater than 110°F (43°C) by a water-temperature-limiting device conforming to ASSE 1070/ASME A112.1070/CSA B125.70.