7.4.9 Bidet Seats for Water Closets
Go To Full Code Chapter
Bidet seats for water closets shall comply with Section 7.4.5 for water closet seats. They shall include the sprays and water controls required by a bidet. They shall comply with ASME A112.4.2/CSA B45.16 for water closet personal hygiene devices, including an equipment-mounted atmospheric vacuum breaker with 1" minimum critical level in accordance with ASSE 1001 or CSA B64.1.1 for high hazards.