457.1.4.12 Bedrooms
JUMP TO FULL CODE CHAPTER
Ceilings shall be nonaccessible to prohibit persons receiving services from entering attic spaces or having access to overhead pipes and beams. Light switches and electrical outlets shall be secured with nontamper-type screws. When feasible each bedroom shall have a window, operable by staff, with an exterior view. Window sills shall not exceed a height of 36 inches (914 mm) above floor level and should incorporate protective screens or Lexan-type material to prevent direct access to glass surfaces. There should be no overhead protrusions available for hanging in excess of 40 pounds (18 kg) weight.
Beds and other heavy furniture suitable for barricading the door shall be secured to the floor or walls.
Multiple occupant bedrooms shall be limited to a maximum of four occupants and shall be a minimum size of 60 square feet (6 m2) per bed with no less than a 30-inch (762 mm) separation between beds. Single occupant bedrooms shall be a minimum of 80 square feet (7 m2).
Bedroom doors shall be a minimum of 36 inches (914 mm) wide.
Related Code Sections
457.1.4.12 Special Detailed Requirements Based on Use and Occupancy, Bedrooms
switches and electrical outlets shall be secured with nontamper-type screws. When feasible, each bedroom shall have a window, operable by staff ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 457 Mental Health Programs > 457.1 Public Mental Health Crisis Stabilization Units and Short-Term Residential Treatment Programs > 457.1.4 Minimum Construction Standards for CSU and SRT Facilities Initially Licensed After July 14, 1993 > 457.1.4.12 Bedrooms
457.1.4.12 Special Detailed Requirements Based on Use and Occupancy, Bedrooms
switches and electrical outlets shall be secured with nontamper-type screws. When feasible each bedroom shall have a window, operable by staff ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 457 Mental Health Programs > 457.1 Public Mental Health Crisis Stabilization Units and Short-Term Residential Treatment Programs > 457.1.4 Minimum Construction Standards for CSU and SRT Facilities Initially Licensed After July 14, 1993 > 457.1.4.12 Bedrooms
457.1.4.12 Special Detailed Requirements Based on Occupancy and Use, Bedrooms
switches and electrical outlets shall be secured with nontamper-type screws. When feasible each bedroom shall have a window, operable by staff ...
2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 457 Mental Health Programs > 457.1 Public Mental Health Crisis Stabilization Units and Short-Term Residential Treatment Programs > 457.1.4 Minimum Construction Standards for CSU and SRT Facilities Initially Licensed After July 14, 1993 > 457.1.4.12 Bedrooms
464.4.4 Special Detailed Requirements Based on Use and Occupancy, Bedrooms
Resident bedrooms designated for multiple occupancy shall provide a minimum inside measurement of 60 square feet (6 m 2 ) of usable ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 464 Assisted Living Facilities > 464.4 Additional Physical Plant Requirements for Assisted Living Facilities > 464.4.4 Bedrooms
464.4.4 Special Detailed Requirements Based on Use and Occupancy, Bedrooms
Resident bedrooms designated for multiple occupancy shall provide a minimum inside measurement of 60 square feet (6 m 2 ) of usable floor ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 464 Assisted Living Facilities > 464.4 Additional Physical Plant Requirements for Assisted Living Facilities > 464.4.4 Bedrooms