R606.3.1 Bed and Head Joints
JUMP TO FULL CODE CHAPTER
Unless otherwise required or indicated on the project drawings, head and bed joints shall be 3/8 inch (9.5 mm) thick, except that the thickness of the bed joint of the starting course placed over foundations shall be not less than 1/4 inch (6.4 mm) and not more than 3/4 inch (19.1 mm). Mortar joint thickness for load-bearing masonry shall be within the following tolerances from the specified dimensions:
- Bed joint: + 1/8 inch (3.2 mm).
- Head joint: - 1/4 inch (6.4 mm), + 3/8 inch (9.5 mm).
- Collar joints: - 1/4 inch (6.4 mm), + 3/8 inch (9.5 mm).
Related Code Sections
R606.3.1 Wall Construction, Bed and Head Joints
Unless otherwise required or indicated on the project drawings, head and bed joints shall be 3 / 8 inch (9.5 mm) thick, except that the thickness ...
Residential Code 2015 of Louisiana > 6 Wall Construction > R606 General Masonry Construction > R606.3 Construction Requirements > R606.3.1 Bed and Head Joints
R607.10 Wall Construction, Placement
Glass units shall be placed so head and bed joints are filled solidly. Mortar shall not be furrowed. Head and bed joints of glass unit masonry shall ...
Residential Code 2015 of Louisiana > 6 Wall Construction > R607 Glass Unit Masonry > R607.10 Placement
2109.3.4.2.2 Masonry, Mortar Joints
Adobe units shall be laid with full head and bed joints and in full running bond ...
Building Code 2015 of Louisiana > 21 Masonry > 2109 Empirical Design of Masonry > 2109.3 Adobe Construction > 2109.3.4 Detailed Requirements > 2109.3.4.2 Mortar > 2109.3.4.2.2 Mortar Joints
A106.3.3.2 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings, Alternative Procedures for Testing Masonry
inches (203 mm) in diameter. A bed joint intersection with a head joint shall be in the center of the core. The tensile-splitting strength of these cores ...
Existing Building Code 2015 of Louisiana > A1 Seismic Strengthening Provisions for Unreinforced Masonry Bearing Wall Buildings > A106 Materials Requirements > A106.3 Existing Unreinforced Masonry > A106.3.3 Testing of Masonry > A106.3.3.2 Alternative Procedures for Testing Masonry
R606.3.7 Wall Construction, Masonry Bonding Pattern
In each wythe of masonry laid in running bond, head joints in successive courses shall be offset by not less ...
Residential Code 2015 of Louisiana > 6 Wall Construction > R606 General Masonry Construction > R606.3 Construction Requirements > R606.3.7 Masonry Bonding Pattern