30.3.4 Battery-Powered Electric Vehicles
JUMP TO FULL CODE CHAPTER
In a repair garage, the required
number, location, and construction of means of egress shall
meet all applicable requirements for special purpose industrial
occupancies, as set forth in NFPA 101, or as determined in
accordance with the adopted building code.
Walls, floors, and structural supports
shall be constructed of masonry, concrete, steel, or other
approved noncombustible materials.
Automatic sprinkler protection installed in accordance with the requirements of Section 13.3 shall be provided
throughout the fire area containing the repair garage.
An automatic smoke detection system shall be
installed throughout the fire area containing the repair garage
in accordance with NFPA 70, NFPA 72, and Section 13.7 of this
Code.
Charging equipment shall be installed in accordance
with NFPA 70.
Related Code Sections
30.3.4 Motor Fuel Dispensing Facilities and Repair Garages, Battery-Powered Electric Vehicles
The occupancy classification of a repair garage shall be a special purpose industrial
occupancy as defined in NFPA 101 , or as determined ...
Fire Code 2021 of Delaware > 30 Motor Fuel Dispensing Facilities and Repair Garages > 30.3 Repair Garages for Vehicles Powered by Alternate Fuels > 30.3.4 Battery-Powered Electric Vehicles
30.3.4.5 Motor Fuel Dispensing Facilities and Repair Garages,
Charging equipment shall be installed in accordance
with NFPA 70 ...
Fire Code 2021 of Delaware > 30 Motor Fuel Dispensing Facilities and Repair Garages > 30.3 Repair Garages for Vehicles Powered by Alternate Fuels > 30.3.4 Battery-Powered Electric Vehicles > 30.3.4.5
30.3.4.4.1 Motor Fuel Dispensing Facilities and Repair Garages,
Automatic sprinkler protection installed in accordance with the requirements of Section 13.3 shall be provided
throughout the fire area containing ...
Fire Code 2021 of Delaware > 30 Motor Fuel Dispensing Facilities and Repair Garages > 30.3 Repair Garages for Vehicles Powered by Alternate Fuels > 30.3.4 Battery-Powered Electric Vehicles > 30.3.4.4 Fixed Fire Protection > 30.3.4.4.1
30.3.4.4.2 Motor Fuel Dispensing Facilities and Repair Garages,
An automatic smoke detection system shall be
installed throughout the fire area containing the repair garage
in accordance with NFPA 70, NFPA 72 ...
Fire Code 2021 of Delaware > 30 Motor Fuel Dispensing Facilities and Repair Garages > 30.3 Repair Garages for Vehicles Powered by Alternate Fuels > 30.3.4 Battery-Powered Electric Vehicles > 30.3.4.4 Fixed Fire Protection > 30.3.4.4.2
30.3.4.4.3 Motor Fuel Dispensing Facilities and Repair Garages,
Emergency forces notification shall be in accordance with 13.7.1.10 ...
Fire Code 2021 of Delaware > 30 Motor Fuel Dispensing Facilities and Repair Garages > 30.3 Repair Garages for Vehicles Powered by Alternate Fuels > 30.3.4 Battery-Powered Electric Vehicles > 30.3.4.4 Fixed Fire Protection > 30.3.4.4.3