End wall vertical grab bars for bathtubs shall comply with all of the following:
  1. Vertical grab bars shall have a length of not less than 36 in. (914 mm).
  2. Vertical grab bars shall be located between 24 in. (610 mm) and 27 in. (686 mm) above the finished floor, measured to the lower end.
  3. Vertical grab bars shall be installed at the end that is least obstructed for entry and egress.
  4. Vertical grab bars shall be located between 9 in. (228 mm) and 12 in. (305 mm) from the open entry and egress side of the bathtub or bathtub-shower combination, measured horizontally from the exterior plane of the bathtub or bathtub-shower combination.