1905.8.2.3 Batch Tickets
JUMP TO FULL CODE CHAPTER
Batch tickets shall accompany every load of concrete delivered to a site. The batch ticket shall contain the information specified in Items 1 through 7:
- Plant name and location.
- Contract number and project.
- Mix designation as to type and strength.
- Each material in the load along with quantities of each by weight.
- The total amount of mix proportion water approved, quantity of water added at the plant and in transit, and the remaining water that can be added on site.
- Any deviations from the approved concrete mix design and variations permitted by Section 1905.3.5.
- The time the water was added to the batch.
A copy of each batch ticket shall be given to the licensed concrete testing laboratory special inspector performing the acceptance testing at the delivery of each load. The licensed laboratory shall maintain copies of the batch tickets along with other inspection reports required by Section 1704.1, and make them available to the department upon request.
Related Code Sections
1905.8.2.3 Concrete, Batch Tickets
Batch tickets shall accompany every load of concrete delivered to a site. The batch ticket shall contain the information specified in Items 1 through ...
NYC Building Code 2014 > 19 Concrete > 1905 Concrete Quality, Mixing and Placing > 1905.8 Mixing > 1905.8.2 Ready-Mixed Concrete > 1905.8.2.3 Batch Tickets
1905.8.2.3 Concrete, Batch Tickets
Batch tickets shall accompany every load of concrete delivered to a site. The batch ticket shall contain the information specified in Items 1 through ...
NYC Building Code 2022 > 19 Concrete > 1905 Concrete Quality, Mixing and Placing > 1905.8 Mixing > 1905.8.2 Ready-Mixed Concrete > 1905.8.2.3 Batch Tickets
1905.6.3.1 Concrete, Mix Design
The special inspector shall verify that the proportions indicated on the batch ticket for the concrete delivered to the construction site are as per ...
NYC Building Code 2014 > 19 Concrete > 1905 Concrete Quality, Mixing and Placing > 1905.6 Evaluation and Acceptance of Concrete > 1905.6.3 Standard-Cured Specimens > 1905.6.3.1 Mix Design
1905.6.3.1 Concrete, Mix Design
The special inspector shall verify that the proportions indicated on the batch ticket for the concrete delivered to the construction site are as per ...
NYC Building Code 2022 > 19 Concrete > 1905 Concrete Quality, Mixing and Placing > 1905.6 Evaluation and Acceptance of Concrete > 1905.6.3 Standard-Cured Specimens > 1905.6.3.1 Mix Design