AF103.4 Basements or Enclosed Crawl Spaces With Concrete Floors or Other Floor Systems and Slab-On-Grade Dwellings
JUMP TO FULL CODE CHAPTER
A soil-gas-retarder shall be
placed on top of the gas-permeable layer prior to casting the slab or placing the floor assembly. The soil-gasretarder
shall cover the entire floor area with separate sections
lapped not less than 12 inches (305 mm). The soilgas-
retarder shall fit closely around any pipe, wire, or
other penetrations of the material. Punctures or tears in the
material shall be sealed or covered.
Before a slab is cast
or other floor system is installed, a "T" fitting shall be
inserted below the slab or other floor system and the soilgas-
retarder. The "T" fitting shall be connected to a vent
pipe. The vent pipe shall extend through the conditioned
space of the dwelling and terminate not less than 12 inches
(305 mm) above the roof in a location not less than 10 feet
(3048 mm) away from any window or other opening into
the conditioned spaces of the building that is less than 2
feet (610 mm) below the exhaust point.
Related Code Sections
AF103.4 Passive Radon Gas Controls, Basements or Enclosed Crawl Spaces With Concrete Floors or Other Floor Systems and Slab-On-Grade Dwellings
or in dwellings with basements or
crawl spaces with concrete or other floor systems ...
2015 Michigan Residential Code > F Passive Radon Gas Controls > AF103 Passive Radon-Resistant System Requirements > AF103.4 Basements or Enclosed Crawl Spaces With Concrete Floors or Other Floor Systems and Slab-On-Grade Dwellings
AF103.2 Passive Radon Gas Controls, Entry Routes
Entry points, joints
or other openings into air-conditioning systems in
enclosed crawl spaces ...
2015 Michigan Residential Code > F Passive Radon Gas Controls > AF103 Passive Radon-Resistant System Requirements > AF103.2 Entry Routes
Section R506 Floors, Concrete Floors (On Ground)
Concrete slab-on-ground floors shall be
designed and constructed in accordance with the provisions
of this section or ACI 332. Floors shall ...
R506.2 Floors, Site Preparation
be placed on the prepared sub-grade where the slab is below grade.
Exception: A base course is not required where the concrete slab is installed ...
2015 Michigan Residential Code > 5 Floors > R506 Concrete Floors (On Ground) > R506.2 Site Preparation
R403.4.2 Foundations, Concrete Footings
Concrete footings shall be
installed in accordance with Section R403.1 and Figure
R403.4(2).
FIGURE R403.4(2)
BASEMENT OR CRAWL SPACE ...
2015 Michigan Residential Code > 4 Foundations > R403 Footings > R403.4 Footings for Precast Concrete Foundations > R403.4.2 Concrete Footings