16.14.5.1* Backflow Prevention Valves
Go To Full Code Chapter
Means shall be provided downstream of all backflow prevention valves for forward flow tests at a minimum flow rate of the system demand including hose allowance where applicable.
16.14.5.1.1
The arrangement required in 16.14.5.1 shall be serviceable without requiring the owner to modify the system to perform the test.
Upcodes Diagrams
Related Code Sections
16.14.5.1* Installation of Piping, Valves, and Appurtenances, Backflow Prevention Valves
Means shall be provided downstream of all backflow prevention valves for forward flow tests at a minimum flow rate of the system demand including ...
8.17.4.5.1* Installation Requirements, Backflow Prevention Valves
Means shall be provided downstream of all backflow prevention valves for forward flow tests at a minimum flow rate of the system demand including ...
8.17.4.6.1* Installation Requirements, Backflow Prevention Valves
Means shall be provided downstream of all backflow prevention valves for flow tests at system demand ...
11.2.2.6.2 Design Approaches, Friction Loss Due to Backflow Prevention Valves
When backflow prevention valves are installed on pipe schedule systems, the friction losses of the device shall be accounted for when determining ...
Standard for the Installation of Sprinkler Systems 2013 of New Jersey > 11 Design Approaches > 11.2 Occupancy Hazard Fire Control Approach for Spray Sprinklers > 11.2.2 Water Demand Requirements — Pipe Schedule Method > 11.2.2.6* Residual Pressure > 11.2.2.6.2 Friction Loss Due to Backflow Prevention Valves
11.2.2.6.2 Design Approaches, Friction Loss Due to Backflow Prevention Valves
When backflow prevention valves are installed on pipe schedule systems, the friction losses of the device shall be accounted for when determining ...
Standard for the Installation of Sprinkler Systems 2016 of New Jersey > 11 Design Approaches > 11.2 Occupancy Hazard Fire Control Approach for Spray Sprinklers > 11.2.2 Water Demand Requirements — Pipe Schedule Method > 11.2.2.6* Residual Pressure > 11.2.2.6.2 Friction Loss Due to Backflow Prevention Valves