Axial geotechnical capacity of piles under static loading shall be evaluated using guidelines for estimating axial pile capacities provided in POLB WDC [6.8] or other appropriate documents. A minimum factor of safety of 2.0 shall be achieved on the ultimate capacity of the pile using appropriate MOT loading.
If liquefaction or seismically-induced settlement is anticipated, the ultimate axial geotechnical capacity of piles under seismic conditions shall be evaluated for the effects of liquefaction and/or downdrag forces on the pile. The ultimate geotechnical capacity of the pile during liquefaction shall be determined on the basis of the residual strength of the soil for those layers where the factor of safety for liquefaction is determined to be less than 1.0.
When seismically-induced settlements are predicted to occur during design earthquakes, the downdrag loads shall be computed, and the combination of downdrag load and static load determined. Only the tip resistance of the pile and the side friction resistance below the lowest layer contributing to the downdrag shall be used in the capacity evaluation. The ultimate axial geotechnical capacity of the pile shall not be less than the combination of the seismically induced downdrag force and the maximum static load.
Upcodes Diagrams

Related Code Sections

3106F.8.1 [SLC] Marine Oil Terminals, Axial Pile Capacity
Axial geotechnical capacity of piles under static loading shall be evaluated using guidelines for estimating axial pile capacities provided in POLB ...
3106F.8.1 [SLC] Marine Oil Terminals, Axial Pile Capacity
Axial geotechnical capacity of piles under static loading shall be evaluated using guidelines for estimating axial pile capacities provided in POLB ...
3106F.8.1 [SLC] Marine Oil Terminals, Axial Pile Capacity
Axial geotechnical capacity of piles under static loading shall be evaluated using guidelines for estimating axial pile capacities provided in POLB ...
1810.3.3.1.9 Soils and Foundations, Helical Piles
determined from well-documented correlations with installation torque. Ultimate capacity determined from load tests. Ultimate axial capacity of pile shaft ...
1810.3.3.1.9 Soils and Foundations, Helical Piles
determined from well-documented correlations with installation torque. Ultimate capacity determined from load tests. Ultimate axial capacity of pile shaft ...