1810.3.8.3.4 Axial Load Limit in Seismic Design Categories C Through F
JUMP TO FULL CODE CHAPTER
For structures assigned to Seismic Design Category C, D, E, or F, the maximum factored axial load on precast prestressed piles subjected to a combination of seismic lateral force and axial load shall not exceed the following values:
- 0.2f 'c Ag for square piles
- 0.4f 'c Ag for circular or octagonal piles
Related Code Sections
1810.3.8.3.4 Soils and Foundations, Axial Load Limit in Seismic Design Categories C Through F
For structures assigned to Seismic Design Category C, D, E, or F, the maximum factored axial load on precast prestressed piles subjected ...
2018 Philadelphia Building Code > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.8 Precast Concrete Piles > 1810.3.8.3 Precast Prestressed Piles > 1810.3.8.3.4 Axial Load Limit in Seismic Design Categories C Through F
1803.5.12 Soils and Foundations, Seismic Design Categories D Through F
For structures assigned to Seismic Design Category D, E or F, the geotechnical investigation required by Section 1803.5.11 shall include all ...
2018 Philadelphia Building Code > 18 Soils and Foundations > 1803 Geotechnical Investigations > 1803.5 Investigated Conditions > 1803.5.12 Seismic Design Categories D Through F
1807.1.6.3.2 Soils and Foundations, Seismic Requirements
1807.1.6.3(1) through 1807.1.6.3(4) shall be subject to the following limitations: Seismic Design Categories A and B. No additional seismic ...
2018 Philadelphia Building Code > 18 Soils and Foundations > 1807 Foundation Walls, Retaining Walls and Embedded Posts and Poles > 1807.1 Foundation Walls > 1807.1.6 Prescriptive Design of Concrete and Masonry Foundation Walls > 1807.1.6.3 Masonry Foundation Walls > 1807.1.6.3.2 Seismic Requirements
2308.2.6 Wood, Risk Category Limitation
assigned to Seismic Design Category B, C, D or F ...
2018 Philadelphia Building Code > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.2 Limitations > 2308.2.6 Risk Category Limitation
2308.2 Wood, Limitations
in this section shall not be permitted for Risk Category IV buildings assigned to Seismic Design Category B, C, D or F ...
2018 Philadelphia Building Code > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.2 Limitations