C405.2.2.1 Automatic Time Switch Control Devices
JUMP TO FULL CODE CHAPTER
Automatic time switch controls shall be installed to control lighting in all areas of the building.
Exception:
The automatic time switch control device shall include an override switching device that complies with the following:
- The override switch shall be in a readily accessible location;
- The override switch shall be located where the lights controlled by the switch are visible; or the switch shall provide a mechanism which announces the area controlled by the switch;
- The override switch shall permit manual operation;
- The override switch, when initiated, shall permit the controlled lighting to remain on for a maximum of 2 hours; and
- Any individual override switch shall control the lighting for a maximum area of 5,000 square feet (465 m2).
Exception:
Within malls, arcades, auditoriums, single tenant retail spaces, industrial facilities and arenas:
- The time limit shall be permitted to exceed 2 hours provided the override switch is a captive key device; and
- The area controlled by the override switch is permitted to exceed 5,000 square feet (465 m2), but shall not exceed 20,000 square feet (1860 m2).
Related Code Sections
C405.2.2.1 [CE] Commercial Energy Efficiency, Automatic Time Switch Control Devices
by automatic time switch controls.
The automatic time switch control device shall include an override switching device that complies ...
DC Energy Conservation Code 2013 > 4 [CE] Commercial Energy Efficiency > C405 Electrical Power and Lighting Systems (Mandatory) > C405.2 Lighting Controls (Mandatory) > C405.2.2 Additional Lighting Controls > C405.2.2.1 Automatic Time Switch Control Devices
909.16.3 Fire Protection Systems, Control Action and Priorities
-position firefighter's control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO ...
DC Fire Code 2017 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities
909.16.3 Fire Protection Systems, Control Action and Priorities
of each three-position firefighter's control panel switch shall allow automatic or manual control action from other control points within the building ...
DC Building Code 2017 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities
909.16.3 Fire Protection Systems, Control Action and Priorities
-position fire-fighter's control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO ...
DC Building Code 2013 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire-Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities
909.16.3 Fire Protection Systems, Control Action and Priorities
fire-fighter's control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO position ...
DC Fire Code 2013 > 9 Fire Protection Systems > 909 Smoke Control Systems > 909.16 Fire-Fighter's Smoke Control Panel > 909.16.3 Control Action and Priorities