Automatic doors and automatic gates shall comply with 404.3.  Full-powered automatic doors shall comply with ANSI/BHMA A156.10 (incorporated by reference, see "Referenced Standards" in Chapter 1).  Low-energy and power-assisted doors shall comply with ANSI/BHMA A156.19 (1997 or 2002 edition) (incorporated by reference, see "Referenced Standards" in Chapter 1).
404.3.1 Clear Width
Doorways shall provide a clear opening of 32 inches (815 mm) minimum in power-on and power-off mode.  The minimum clear width for automatic door systems in a doorway shall be based on the clear opening provided by all leaves in the open position.
404.3.2 Maneuvering Clearance
Clearances at power-assisted doors and gates shall comply with 404.2.4. Clearances at automatic doors and gates without standby power and serving an accessible means of egress shall comply with 404.2.4.

EXCEPTION: Where automatic doors and gates remain open in the power-off condition, compliance with 404.2.4 shall not be required.
404.3.3 Thresholds
Thresholds and changes in level at doorways shall comply with 404.2.5.
404.3.4 Doors in Series and Gates in Series
Doors in series and gates in series shall comply with 404.2.6.
404.3.5 Controls
Manually operated controls shall comply with 309.  The clear floor space adjacent to the control shall be located beyond the arc of the door swing.
404.3.6 Break Out Opening
Where doors and gates without standby power are a part of a means of egress, the clear break out opening at swinging or sliding doors and gates shall be 32 inches (815 mm) minimum when operated in emergency mode.

EXCEPTION: Where manual swinging doors and gates comply with 404.2 and serve the same means of egress compliance with 404.3.6 shall not be required.
404.3.7 Revolving Doors, Revolving Gates, and Turnstiles
Revolving doors, revolving gates, and turnstiles shall not be part of an accessible route.

Related Code Sections

404.3 Accessible Routes, Automatic and Power-Assisted Doors and Gates
Automatic doors and automatic gates shall comply with 404.3.  Full-powered automatic doors shall comply with ANSI/BHMA A156.10 (incorporated ...
404.3.6 Accessible Routes, Break Out Opening
Where doors and gates without standby power are a part of a means of egress, the clear break out opening at swinging or sliding doors and gates shall ...
404 Accessible Routes, Doors, Doorways, and Gates
Clearances at power-assisted doors and gates shall comply with 404.2.4. Clearances at automatic ...
410.6 Accessible Routes, Doors and Gates
Platform lifts shall have low-energy power-operated doors or gates complying with 404.3. Doors shall remain open for 20 seconds minimum. End doors ...