1504.3.3.3 Automated Spraying Operations
JUMP TO FULL CODE CHAPTER
The fire extinguishing system for each spray room or spray booth designed for automatic spraying operations shall be equipped with an interlock in accordance with FC1504.3.5(7) and with a manual shutdown device. Such manual shutdown device shall be located within the path of emergency egress from such spray room or spray booth, shall be readily accessible to personnel supervising the spraying operation, and when activated, shall initiate the same functions as the automatic interlock.
Related Code Sections
502.7.3 Exhaust Systems, Spraying Areas
times while spraying operations are being conducted and for a sufficient time thereafter to allow vapors from drying coated articles and finishing ...
NYC Mechanical Code 2008 > 5 Exhaust Systems > 502 Required Systems > 502.7 Application of Flammable Finishes > 502.7.3 Spraying Areas
416.4 Special Detailed Requirements Based on Use and Occupancy, Spray Booths
Spray booths shall be designed, constructed and operated in accordance with the New York City Fire Code ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 416 Application of Flammable Finishes > 416.4 Spray Booths
502.7.3.1 Exhaust Systems, Operation
Mechanical ventilation shall be kept in operation at all times while spraying operations are being conducted and for a sufficient time thereafter ...
NYC Mechanical Code 2014 > 5 Exhaust Systems > 502 Required Systems > 502.7 Application of Flammable Finishes > 502.7.3 Flammable Vapor Areas > 502.7.3.1 Operation
412.6.3 Special Detailed Requirements Based on Use and Occupancy, Operations
control area in Table 307.1(1). Spray equipment cleaning operations shall be conducted in a liquid use, dispensing and mixing room ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 412 Aircraft-Related Occupancies > 412.6 Aircraft Paint Hangars > 412.6.3 Operations
3110.3 Special Construction, Vehicular Gates Intended for Automation
Vehicular gates intended for automation shall be designed, constructed and installed to comply with the class of gate in accordance ...
NYC Building Code 2014 > 31 Special Construction > 3110 Automatic Vehicular Gates > 3110.3 Vehicular Gates Intended for Automation