High-piled storage areas with automated rack storage shall be provided with a manually activated emergency shutdown switch and automatic shutdown in accordance with Sections 3209.4.1 and 3209.4.2.
3209.4.1 Manual Activated Shutdown
A manually activated switch shall be provided to initiate the approved automatic shutdown process. The switch shall be clearly identified and shall be in a location approved by the fire code official.
3209.4.2 Automatic Shutdown
Automatic shutdown shall be required for high-piled combustible storage areas greater than 500 square feet (46 m2). The approved automatic shutdown process shall commence upon any of the following events:
  1. Water flow is detected in the automatic sprinkler system, if present.
  2. Activation of the fire detection system, if present.

Related Code Sections

3209.4 High-Piled Combustible Storage, Automated Rack Storage
High-piled storage areas with automated rack storage shall be provided with a manually activated emergency shutdown switch for use by emergency ...
3209.4 High-Piled Combustible Storage, Automated Rack Storage
High-piled storage areas with automated rack storage shall be provided with a manually activated emergency shutdown switch and automatic shutdown ...
Section 3202 High-Piled Combustible Storage, Definitions
The following terms are defined in Chapter 2: ARRAY. ARRAY, CLOSED. AUTOMATED RACK STORAGE. BIN BOX. COMMODITY. EARLY SUPPRESSION FAST-RESPONSE ...
Section 3202 High-Piled Combustible Storage, Definitions
The following terms are defined in Chapter 2: ARRAY. ARRAY, CLOSED. AUTOMATED RACK STORAGE. BIN BOX. COMMODITY. EARLY SUPPRESSION FAST ...
Section 3209 High-Piled Combustible Storage, Automated Storage
High-piled storage areas with automated rack storage shall be provided with a manually activated ...