69.5.6 Automated Cylinder Exchange Stations
JUMP TO FULL CODE CHAPTER
Electrical equipment installed in cylinder storage compartments shall comply with the requirements for Class I, Division 2 equipment in accordance with NFPA 70, National Electrical Code. [58:8.6.2]
Cabinets shall be designed such that cylinders can be placed inside only in the upright position. [58:8.6.3]
Door releases for access to stored cylinders shall be permitted to be pneumatic, mechanical, or electrically powered. [58:8.6.4]
A manual override control shall be permitted for use by authorized personnel. [58:8.6.5]
Related Code Sections
69.5.6 Liquefied Petroleum Gases and Liquefied Natural Gases, Automated Cylinder Exchange Stations
Cylinder exchange cabinets that include an automated vending system for exchanging cylinders shall comply with the requirements in 69.5.6.2 through ...
Fire Code 2015 of Delaware > 69 Liquefied Petroleum Gases and Liquefied Natural Gases > 69.5 Storage of Cylinders Awaiting Use, Resale, or Exchange > 69.5.6 Automated Cylinder Exchange Stations
69.5.6.6 Liquefied Petroleum Gases and Liquefied Natural Gases,
The vending system shall not be capable of returning to automatic operation after a manual override until the system has been inspected and reset ...
Fire Code 2015 of Delaware > 69 Liquefied Petroleum Gases and Liquefied Natural Gases > 69.5 Storage of Cylinders Awaiting Use, Resale, or Exchange > 69.5.6 Automated Cylinder Exchange Stations > 69.5.6.6
69.5.1 Liquefied Petroleum Gases and Liquefied Natural Gases, Scope
, or empty, as follows: At consumer sites or dispensing stations, where not connected for use In storage for resale or exchange by dealer or reseller ...
Fire Code 2015 of Delaware > 69 Liquefied Petroleum Gases and Liquefied Natural Gases > 69.5 Storage of Cylinders Awaiting Use, Resale, or Exchange > 69.5.1 Scope
69.5 Liquefied Petroleum Gases and Liquefied Natural Gases, Storage of Cylinders Awaiting Use, Resale, or Exchange
exchange cabinets that include an automated vending system for exchanging cylinders shall comply ...
Fire Code 2015 of Delaware > 69 Liquefied Petroleum Gases and Liquefied Natural Gases > 69.5 Storage of Cylinders Awaiting Use, Resale, or Exchange
69.5.1.1 Liquefied Petroleum Gases and Liquefied Natural Gases,
, or empty, as follows: At consumer sites or dispensing stations, where not connected for use In storage for resale or exchange by dealer or reseller ...
Fire Code 2015 of Delaware > 69 Liquefied Petroleum Gases and Liquefied Natural Gases > 69.5 Storage of Cylinders Awaiting Use, Resale, or Exchange > 69.5.1 Scope > 69.5.1.1