603.5.1 Atmospheric Vacuum Breaker
JUMP TO FULL CODE CHAPTER
Water closet
and urinal flushometer valves shall be protected against
backflow by an approved backflow prevention assembly,
device, or method. Where the valves are equipped
with an atmospheric vacuum breaker, the vacuum
breaker shall be installed on the discharge side of the
flushometer valve with the critical level not less than 6
inches (152 mm), or the distance according to its listing,
above the overflow rim of a water closet bowl or
the highest part of a urinal.