1926.404(b)(1)(iii) Assured Equipment Grounding Conductor Program
JUMP TO FULL CODE CHAPTER
The employer shall establish and implement an assured equipment grounding conductor program on construction sites covering all cord sets, receptacles which are not a part of the building or structure, and equipment connected by cord and plug which are available for use or used by employees. This program shall comply with the following minimum requirements:
A written description of the program, including the specific procedures adopted by the employer, shall be available at the jobsite for inspection and copying by the Assistant Secretary and any affected employee.
The employer shall designate one or more competent persons (as defined in 1926.32(f)) to implement the program.
Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which are fixed and not exposed to damage, shall be visually inspected before each day's use for external defects, such as deformed or missing pins or insulation damage, and for indications of possible internal damage. Equipment found damaged or defective shall not be used until repaired.
The following tests shall be performed on all cord sets, receptacles which are not a part of the permanent wiring of the building or structure, and cord- and plug-connected equipment required to be grounded:
All equipment grounding conductors shall be tested for continuity and shall be electrically continuous.
Each receptacle and attachment cap or plug shall be tested for correct attachment of the equipment grounding conductor. The equipment grounding conductor shall be connected to its proper terminal.
All required tests shall be performed:
Before first use;
Before equipment is returned to service following any repairs;
Before equipment is used after any incident which can be reasonably suspected to have caused damage (for example, when a cord set is run over); and
At intervals not to exceed 3 months, except that cord sets and receptacles which are fixed and not exposed to damage shall be tested at intervals not exceeding 6 months.
The employer shall not make available or permit the use by employees of any equipment which has not met the requirements of this paragraph (b)(1)(iii) of this section.
Tests performed as required in this paragraph shall be recorded. This test record shall identify each receptacle, cord set, and cord- and plug-connected equipment that passed the test and shall indicate the last date it was tested or the interval for which it was tested. This record shall be kept by means of logs, color coding, or other effective means and shall be maintained until replaced by a more current record. The record shall be made available on the jobsite for inspection by the Assistant Secretary and any affected employee.
Related Code Sections
1926.404(b)(1)(iii) Electrical, Assured Equipment Grounding Conductor Program
The employer shall establish and implement an assured equipment grounding conductor program on construction sites covering all cord sets, receptacles ...
OSHA 1926 Construction > K Electrical > 1926.404 Wiring Design and Protection > 1926.404(b) Branch Circuits > 1926.404(b)(1) Ground-Fault Protection > 1926.404(b)(1)(iii) Assured Equipment Grounding Conductor Program
1926.404(b)(1)(iii)(C) Electrical,
Each cord set, attachment cap, plug and receptacle of cord sets, and any equipment connected by cord and plug, except cord sets and receptacles which ...
OSHA 1926 Construction > K Electrical > 1926.404 Wiring Design and Protection > 1926.404(b) Branch Circuits > 1926.404(b)(1) Ground-Fault Protection > 1926.404(b)(1)(iii) Assured Equipment Grounding Conductor Program > 1926.404(b)(1)(iii)(C)
1926.404(b)(1)(iii)(E) Electrical,
first use; Before equipment is returned to service ...
OSHA 1926 Construction > K Electrical > 1926.404 Wiring Design and Protection > 1926.404(b) Branch Circuits > 1926.404(b)(1) Ground-Fault Protection > 1926.404(b)(1)(iii) Assured Equipment Grounding Conductor Program > 1926.404(b)(1)(iii)(E)
1926.404(b)(1)(iii)(E)(2) Electrical,
Before equipment is returned to service following any repairs; ...
OSHA 1926 Construction > K Electrical > 1926.404 Wiring Design and Protection > 1926.404(b) Branch Circuits > 1926.404(b)(1) Ground-Fault Protection > 1926.404(b)(1)(iii) Assured Equipment Grounding Conductor Program > 1926.404(b)(1)(iii)(E) > 1926.404(b)(1)(iii)(E)(2)
1926.404(b)(1)(iii)(E)(3) Electrical,
Before equipment is used after any incident which can be reasonably suspected to have caused damage (for example, when a cord set is run over); and ...
OSHA 1926 Construction > K Electrical > 1926.404 Wiring Design and Protection > 1926.404(b) Branch Circuits > 1926.404(b)(1) Ground-Fault Protection > 1926.404(b)(1)(iii) Assured Equipment Grounding Conductor Program > 1926.404(b)(1)(iii)(E) > 1926.404(b)(1)(iii)(E)(3)