// CODE SNIPPET
Article 320 Armored Cable: Type AC
Go To Full Code Chapter
320.1 Scope
This article covers the use, installation, and construction specifications for armored cable, Type AC.
320.2 Definition
The definition in this section shall apply within this article and throughout the Code.
Armored Cable, Type AC. A fabricated assembly of insulated conductors in a flexible interlocked metallic armor. See 320.100.
320.10 Uses Permitted
Type AC cable shall be permitted as follows:
- For feeders and branch circuits in both exposed and concealed installations
- In cable trays
- In dry locations
- Embedded in plaster finish on brick or other masonry, except in damp or wet locations
- To be run or fished in the air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampness
Informational Note: The "Uses Permitted" is not an all-inclusive list.
320.12 Uses Not Permitted
Type AC cable shall not be used as follows:
- Where subject to physical damage
- In damp or wet locations
- In air voids of masonry block or tile walls where such walls are exposed or subject to excessive moisture or dampness
- Where exposed to corrosive conditions
- Embedded in plaster finish on brick or other masonry in damp or wet locations
320.15 Exposed Work
320.17 Through or Parallel to Framing Members
320.23 In Accessible Attics
Type AC cables in accessible attics or roof spaces shall be installed as specified in 320.23(A) and (B).
(A) Cables Run Across the Top of Floor Joists
Where run across the top of floor joists, or within 2.1 m (7 ft) of the floor or floor joists across the face of rafters or studding, the cable shall be protected by guard strips that are at least as high as the cable. Where this space is not accessible by permanently installed stairs or ladders, protection shall only be required within 1.8 m (6 ft) of the nearest edge of the scuttle hole or attic entrance.
(B) Cable Installed Parallel to Framing Members
320.24 Bending Radius
320.30 Securing and Supporting
(A) General
(B) Securing
(C) Supporting
Unless otherwise permitted, Type AC cable shall be supported at intervals not exceeding 1.4 m (41/2 ft).
Horizontal runs of Type AC cable installed in wooden or metal framing members or similar supporting means shall be considered supported and secured where such support does not exceed 1.4 m (41/2 ft) intervals.
(D) Unsupported Cables
Type AC cable shall be permitted to be unsupported and unsecured where the cable complies with any of the following:
- Is fished between access points through concealed spaces in finished buildings or structures and supporting is impracticable
- Is not more than 600 mm (2 ft) in length at terminals where flexibility is necessary
- Is not more than 1.8 m (6 ft) in length from the last point of cable support to the point of connection to a luminaire(s) or other electrical equipment and the cable and point of connection are within an accessible ceiling
320.40 Boxes and Fittings
At all points where the armor of AC cable terminates, a fitting shall be provided to protect wires from abrasion, unless the design of the outlet boxes or fittings is such as to afford equivalent protection, and, in addition, an insulating bushing or its equivalent protection shall be provided between the conductors and the armor. The connector or clamp by which the Type AC cable is fastened to boxes or cabinets shall be of such design that the insulating bushing or its equivalent will be visible for inspection. Where change is made from Type AC cable to other cable or raceway wiring methods, a box, fitting, or conduit body shall be installed at junction points as required in 300.15.
(A) Thermal Insulation
Armored cable installed in thermal insulation shall have conductors rated at 90°C (194°F). The ampacity of cable installed in these applications shall not exceed that of a 60°C (140°F) rated conductor. The 90°C (194°F) rating shall be permitted to be used for ampacity adjustment and correction calculations; however, the ampacity shall not exceed that of a 60°C (140°F) rated conductor.
Where more than two Type AC cables containing two or more current-carrying conductors in each cable are installed in contact with thermal insulation, caulk, or sealing foam without maintaining spacing between cables, the ampacity of each conductor shall be adjusted in accordance with Table 310.15(C)(1).
(B) Cable Tray
320.100 Construction
320.104 Conductors
Insulated conductors shall be of a type listed in Table 310.4(A) or those identified for use in this cable. In addition, the conductors shall have an overall moisture-resistant and fire-retardant fibrous covering. For Type ACT, a moisture-resistant fibrous covering shall be required only on the individual conductors.
320.108 Equipment Grounding Conductor
Type AC cable shall provide an adequate path for fault current as required by 250.4(A)(5) or (B)(4) to act as an equipment grounding conductor.
Upcodes Diagrams
Related Code Sections
Article 320 Wiring Methods and Materials, Armored Cable: Type AC
This article covers the use, installation, and construction specifications for armored cable, Type AC ...
Article 320 Wiring Methods and Materials, Armored Cable: Type AC
This article covers the use, installation, and construction specifications for armored cable, Type AC ...
320.40 Wiring Methods and Materials, Boxes and Fittings
between the conductors and the armor. The connector or clamp by which the Type AC cable is fastened to boxes or cabinets shall be of such design ...
320.2 Wiring Methods and Materials, Definition
Armored Cable, Type AC. A fabricated assembly of insulated conductors in a flexible interlocked metallic armor. See 320.100 ...
320.80 Wiring Methods and Materials, Ampacity
and correction calculations; however, the ampacity shall not exceed that of a 60°C (140°F) rated conductor. Where more than two Type AC cables containing two ...