// CODE SNIPPET
1004.5 Areas Without Fixed Seating
JUMP TO FULL CODE CHAPTER
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. For areas without fixed seating, the occupant load shall be not less than that number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.5. Where an intended function is not listed in Table 1004.5, the building official shall establish a function based on a listed function that most nearly resembles the intended function.
Exception: Where approved by the building official, the actual number of occupants for whom each occupied space, floor or building is designed, although less than those determined by calculation, shall be permitted to be used in the determination of the design occupant load.
FUNCTION OF SPACE | OCCUPANT LOAD FACTORa |
Accessory storage areas, mechanical equipment room | 300 gross |
Agricultural building | 300 gross |
Aircraft hangars | 500 gross |
Airport terminal | |
Baggage claim |
20 gross |
Baggage handling |
300 gross |
Concourse |
100 gross |
Waiting areas |
15 gross |
Assembly | |
Gaming floors (keno, slots, etc.) |
11 gross |
Exhibit gallery and museum |
30 net |
Assembly with fixed seats | See Section 1004.6 |
Assembly without fixed seats | |
Concentrated (chairs only—not fixed) |
7 net |
Standing space |
5 net |
Unconcentrated (tables and chairs) |
15 net |
Bowling centers, allow 5 persons for each lane including 15 feet of runway, and for additional areas | 7 net |
Business areas | 150 gross |
Concentrated business use areas | See Section 1004.8 |
Courtrooms—other than fixed seating areas | 40 net |
Day care | 35 net |
Dormitories | 50 gross |
Educational | |
Classroom area |
20 net |
Shops and other vocational room areas |
50 net |
Exercise rooms | 50 gross |
Group H-5 fabrication and manufacturing areas | 200 gross |
Industrial areas | 100 gross |
Institutional areas | |
Inpatient treatment areas |
240 gross |
Outpatient areas |
100 gross |
Sleeping areas |
120 gross |
Kitchens, commercial | 200 gross |
Library | |
Reading rooms |
50 net |
Stack area |
100 gross |
Locker rooms | 50 gross |
Mall buildings—covered and open | See Section 402.8.2 |
Mercantile | 60 gross |
Storage, stock, shipping areas | 300 gross |
Parking garages | 200 gross |
Residential | 200 gross |
Skating rinks, swimming pools | |
Rink and pool |
50 gross |
Decks |
15 gross |
Stages and platforms | 15 net |
Warehouses | 500 gross |
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
- Floor area in square feet per occupant.
The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are met based on such modified number and the occupant load does not exceed one occupant per 7 square feet (0.65 m2) of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted.
Related Code Sections
1004.5 Means of Egress, Areas Without Fixed Seating
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. For areas without fixed ...
Building Code 2018 of Illinois > 10 Means of Egress > 1004 Occupant Load > 1004.5 Areas Without Fixed Seating
1004.5 Means of Egress, Areas Without Fixed Seating
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. For areas without fixed ...
Building Code 2021 of Illinois > 10 Means of Egress > 1004 Occupant Load > 1004.5 Areas Without Fixed Seating
Section 1004 Means of Egress, Occupant Load
of area as prescribed in Table 1004.5. For areas without fixed seating , the occupant load shall be not less than that number determined by dividing ...
206.2.4 Scoping Requirements, Spaces and Elements
areas with fixed seating required to comply with 221, an accessible route shall not be required to serve fixed seating where wheelchair spaces ...
2018 Illinois Accessibility Code > 2 Scoping Requirements > 206 Accessible Routes > 206.2 Where Required > 206.2.4 Spaces and Elements
221.5 Scoping Requirements, Lawn Seating
Lawn seating areas and exterior overflow seating areas, where fixed seats are not provided, shall connect to an accessible route ...