2403.2.1.3 Areas Adjacent to Spray Booths
JUMP TO FULL CODE CHAPTER
Electrical wiring and equipment located outside of, but within 3 feet (914 mm) of openings in a spray booth or a spray room, shall be approved for Class I, Division 2 or Class II, Division 2 hazardous locations, whichever is applicable.
Related Code Sections
1503.2.1.3 Flammable Finishes, Areas Adjacent to Spray Booths
booth or a spray room, shall be approved for Class I, Division 2 or Class II, Division 2 hazardous locations, whichever is applicable ...
Philadelphia Fire Code > 15 Flammable Finishes > 1503 Protection of Operations > 1503.2 Sources of Ignition > 1503.2.1 Electrical Wiring and Equipment > 1503.2.1.3 Areas Adjacent to Spray Booths
2403.2.1.3 Flammable Finishes, Areas Adjacent to Spray Booths
Electrical wiring and equipment located outside of, but within 3 feet (914 mm) of openings in a spray booth or a spray room, shall be approved ...
2018 Philadelphia Fire Code > 24 Flammable Finishes > 2403 Protection of Operations > 2403.2 Sources of Ignition > 2403.2.1 Electrical Wiring and Equipment > 2403.2.1.3 Areas Adjacent to Spray Booths
(3) Special Occupancies, Open-Top Spray Booths
; Class I, Zone 2; Class II, Division 2; or Zone 22 Locations Adjacent to a Closed Top, Open Face, or Open Front Spray Booth or Room. [33:Figure 6.5.2] ...
National Electrical Code 2017 of Philadelphia > 5 Special Occupancies > 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials > 516.5 Area Classification > (D) Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 Locations > (3) Open-Top Spray Booths
(4) Special Occupancies, Enclosed Spray Booths and Spray Rooms
For spraying operations confined to an enclosed spray booth or room, electrical area classification shall be as follows: [ 33: 6.5.4] The area ...
National Electrical Code 2014 of Philadelphia > 5 Special Occupancies > 516 Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials > 516.3 Classification of Locations > (D) Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 Locations > (4) Enclosed Spray Booths and Spray Rooms
1504.3.2 Flammable Finishes, Spray Booths
The aggregate area of spray booths in a building shall not exceed the lesser of 10 percent ...
Philadelphia Fire Code > 15 Flammable Finishes > 1504 Spray Finishing > 1504.3 Design and Construction > 1504.3.2 Spray Booths