[F] 907.2.13.1.1 Area Smoke Detection
JUMP TO FULL CODE CHAPTER
Area smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall activate the emergency voice/alarm communication system in accordance with Section 907.5.2.2. In addition to smoke detectors required by Sections 907.2.1 through 907.2.10, smoke detectors shall be located as follows:
- In each mechanical equipment, electrical, transformer, telephone equipment or similar room that is not provided with sprinkler protection.
- In each elevator machine room, machinery space, control room and control space and in elevator lobbies.
Related Code Sections
907.2.12.1.1 Fire Protection and Life Safety Systems, Area Smoke Detection
Area smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The ...
Building Code 2018 of Utah > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.12 High-Rise Buildings > 907.2.12.1 Automatic Smoke Detection > 907.2.12.1.1 Area Smoke Detection
907.2.12.1.1 Fire Protection and Life Safety Systems, Area Smoke Detection
Area smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The ...
Fire Code 2018 of Utah > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.12 High-Rise Buildings > 907.2.12.1 Automatic Smoke Detection > 907.2.12.1.1 Area Smoke Detection
907.2.13.1.1 Fire Protection Systems, Area Smoke Detection
Area smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The ...
Building Code 2015 of Utah > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.13 High-Rise Buildings > 907.2.13.1 Automatic Smoke Detection > 907.2.13.1.1 Area Smoke Detection
607.3.3.3 Duct Systems, Combination Fire/Smoke Damper Actuation
in smoke control system shaft penetrations shall not be activated by local area smoke detection unless it is secondary to the smoke management system ...
Mechanical Code 2015 of Utah > 6 Duct Systems > 607 Duct and Transfer Openings > 607.3 Damper Testing, Ratings and Actuation > 607.3.3 Damper Actuation > 607.3.3.3 Combination Fire/Smoke Damper Actuation
607.3.3.3 Duct Systems, Combination Fire/Smoke Damper Actuation
in smoke control system shaft penetrations shall not be activated by local area smoke detection unless it is secondary to the smoke management system ...
Mechanical Code 2018 of Utah > 6 Duct Systems > 607 Duct and Transfer Openings > 607.3 Damper Testing, Ratings and Actuation > 607.3.3 Damper Actuation > 607.3.3.3 Combination Fire/Smoke Damper Actuation