The building area and type of construction of covered mall or open mall buildings, anchor buildings and parking garages shall comply with this section.
402.4.1.1 Covered and Open Mall Buildings
The building area of any covered mall or open mall building shall not be limited provided that the covered mall or open mall building does not exceed three floor levels at any point nor three stories above grade plane, and is of Type I, II, III or IV construction.
402.4.1.2 Anchor Buildings
The building area and building height of any anchor building shall be based on the type of construction as required by Section 503 as modified by Sections 504 and 506.
Exception: The building area of any anchor building shall not be limited provided that the anchor building is not more than three stories above grade plane, and is of Type I, II, III or IV construction.
402.4.1.3 Parking Garage
The building area and building height of any parking garage shall be based on the type of construction as required by Sections 406.5 and 406.6, respectively.