(ii) 3405.3.6.2 Approved Machines
Parts cleaning and degreasing conducted in approved machines in accordance with paragraph (E)(3)(f)(i)(3405.3.6.1) of this rule shall be in accordance with paragraphs (E)(3)(f)(ii)(a)(3405.3.6.2.1) to (E)(3)(f)(ii)(g) (3405.3.6.2.7) of this rule.
(a) 3405.3.6.2.1 Solvents.
Solvents shall be classified and shall be compatible with the machines within which they are used.
(b) 3405.3.6.2.2 Machine capacities.
The quantity of solvent shall not exceed the listed design capacity of the machine for the solvent being used with the machine.
(c) 3405.3.6.2.3 Solvent quantity limits.
Solvent quantities shall be limited as follows:
(i) Machines without remote solvent reservoirs shall be limited to quantities set forth in paragraph (E)(3)(e)(3405.3.5) of this rule.
(ii) Machines with remote solvent reservoirs using Class I liquids shall be limited to quantities set forth in paragraph (E)(3)(e)(3405.3.5) of this rule.
(iii) Machines with remote solvent reservoirs using Class II liquids shall be limited to 35 gallons (132 L) per machine. The total quantities shall not exceed an aggregate of 240 gallons (908 L) per control area in buildings not equipped throughout with an automatic sprinkler system in accordance with rule 1301:7-7-09 of the Administrative Code. The total quantities shall not exceed an aggregate of 480 gallons (1817 L) per control area in buildings equipped throughout with an automatic sprinkler system in accordance with paragraph (C)(3)(a)(i)(903.3.1.1) of rule 1301:7-7-09 of the Administrative Code.
(iv) Machines with remote solvent reservoirs using Class IIIA liquids shall be limited to 80 gallons (303 L) per machine.
(d) 3405.3.6.2.4 Immersion soaking of parts.
Work areas of machines with remote solvent reservoirs shall not be used for immersion soaking of parts.
(e) 3405.3.6.2.5 Separation.
Multiple machines shall be separated from each other by a distance of not less than 30 feet (9144 mm) or by a fire barrier with a minimum 1 hour fire-resistance rating.
(f) 3405.3.6.2.6 Ventilation.
Machines shall be located in areas adequately ventilated to prevent accumulation of vapors.
(g) 3405.3.6.2.7 Installation.
Machines shall be installed in accordance with their listings.