Section 1703 Approvals

Building Code 2015 of Utah > 17 Special Inspections and Tests > 1703 Approvals
JUMP TO FULL CODE CHAPTER

1703.1 Approved Agency

An approved agency shall provide all information as necessary for the building official to determine that the agency meets the applicable requirements specified in Sections 1703.1.1 through 1703.1.3.

1703.1.1 Independence

An approved agency shall be objective, competent and independent from the contractor responsible for the work being inspected. The agency shall also disclose to the building official and the registered design professional in responsible charge possible conflicts of interest so that objectivity can be confirmed.

1703.1.2 Equipment

An approved agency shall have adequate equipment to perform required tests. The equipment shall be periodically calibrated.

1703.1.3 Personnel

An approved agency shall employ experienced personnel educated in conducting, supervising and evaluating tests and special inspections.

1703.2 Written Approval

Any material, appliance, equipment, system or method of construction meeting the requirements of this code shall be approved in writing after satisfactory completion of the required tests and submission of required test reports.

1703.3 Record of Approval

For any material, appliance, equipment, system or method of construction that has been approved, a record of such approval, including the conditions and limitations of the approval, shall be kept on file in the building official's office and shall be available for public review at appropriate times.

1703.4 Performance

Specific information consisting of test reports conducted by an approved agency in accordance with the appropriate referenced standards, or other such information as necessary, shall be provided for the building official to determine that the product, material or assembly meets the applicable code requirements.

1703.4.1 Research and Investigation

Sufficient technical data shall be submitted to the building official to substantiate the proposed use of any product, material or assembly. If it is determined that the evidence submitted is satisfactory proof of performance for the use intended, the building official shall approve the use of the product, material or assembly subject to the requirements of this code. The costs, reports and investigations required under these provisions shall be paid by the owner or the owner's authorized agent.

1703.4.2 Research Reports

Supporting data, where necessary to assist in the approval of products, materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.

1703.5 Labeling

Products, materials or assemblies required to be labeled shall be labeled in accordance with the procedures set forth in Sections 1703.5.1 through 1703.5.4.

1703.5.1 Testing

An approved agency shall test a representative sample of the product, material or assembly being labeled to the relevant standard or standards. The approved agency shall maintain a record of the tests performed. The record shall provide sufficient detail to verify compliance with the test standard.

1703.5.2 Inspection and Identification

The approved agency shall periodically perform an inspection, which shall be in-plant if necessary, of the product or material that is to be labeled. The inspection shall verify that the labeled product, material or assembly is representative of the product, material or assembly tested.

1703.5.3 Label Information

The label shall contain the manufacturer's identification, model number, serial number or definitive information describing the performance characteristics of the product, material or assembly and the approved agency's identification.

1703.5.4 Method of Labeling

Information required to be permanently identified on the product, material or assembly shall be acid etched, sand blasted, ceramic fired, laser etched, embossed or of a type that, once applied, cannot be removed without being destroyed.

1703.6 Evaluation and Follow-Up Inspection Services

Where structural components or other items regulated by this code are not visible for inspection after completion of a prefabricated assembly, the owner or the owner's authorized agent shall submit a report of each prefabricated assembly. The report shall indicate the complete details of the assembly, including a description of the assembly and its components, the basis upon which the assembly is being evaluated, test results and similar information and other data as necessary for the building official to determine conformance to this code. Such a report shall be approved by the building official.

1703.6.1 Follow-Up Inspection

The owner or the owner's authorized agent shall provide for special inspections of fabricated items in accordance with Section 1704.2.5.

1703.6.2 Test and Inspection Records

Copies of necessary test and special inspection records shall be filed with the building official.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


1003.2 Traps, Interceptors and Separators, Approval
The size, type and location of each interceptor and of each separator shall be designed and installed in accordance with the manufacturer's ...
Plumbing Code 2015 of Utah > 10 Traps, Interceptors and Separators > 1003 Interceptors and Separators > 1003.2 Approval
Section 105 Scope and Administration, Approval
by this code, provided that any such alternative has been approved . An alternative material or method of construction shall be approved where ...
Mechanical Code 2015 of Utah > 1 Scope and Administration > 105 Approval
Section 105 Scope and Administration, Approval
prescribed by this code, provided that any such alternative has been approved. An alternative material or method of construction shall be approved where ...
Plumbing Code 2015 of Utah > 1 Scope and Administration > 105 Approval
107.4 Scope and Administration, Approval
After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued ...
Mechanical Code 2015 of Utah > 1 Scope and Administration > 107 Inspections and Testing > 107.4 Approval
107.4 Scope and Administration, Approval
After the prescribed tests and inspections indicate that the work complies in all respects with this code, a notice of approval shall be issued ...
Fuel Gas Code 2015 of Utah > 1 Scope and Administration > 107 (IFGC) Inspections and Testing > 107.4 Approval
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US