• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

603.2 Approval of Devices or Assemblies

2021 Oregon Plumbing Specialty Code > 6 Water Supply and Distribution > 603.0 Cross-Connection Control > 603.2 Approval of Devices or Assemblies
JUMP TO FULL CODE CHAPTER
Before a device or an assembly is installed for the prevention of backflow, it shall have first been approved by the Authority Having Jurisdiction. Devices or assemblies shall be tested in accordance with recognized standards or other standards acceptable to the Authority Having Jurisdiction. Backflow prevention devices and assemblies shall comply with Table 603.2, except for specific applications and provisions as stated in Section 603.5.1 through Section 603.5.21.
Devices or assemblies installed in a potable water supply system for protection against backflow shall be maintained in good working condition by the person or persons having control of such devices or assemblies. Such devices or assemblies shall be tested at the time of installation, repair, or relocation and not less than on an annual schedule thereafter, or more often where required by the Authority Having Jurisdiction. Where found to be defective or inoperative, the device or assembly shall be repaired or replaced. No device or assembly shall be removed from use or relocated or other device or assembly substituted, without the approval of the Authority Having Jurisdiction.
Testing or maintenance shall be performed by a certified backflow assembly tester or repairer in accordance with ASSE Series 5000 or otherwise approved by the Authority Having Jurisdiction.

TABLE 603.2
BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS
DEGREE OF HAZARD
DEVICE, ASSEMBLY, OR METHOD1 APPLICABLE STANDARDS POLLUTION (LOW HAZARD) CONTAMINATION (HIGH HAZARD) INSTALLATION2,3
BACKSIPHONAGE BACKPRESSURE BACKSIPHONAGE BACKPRESSURE
Air gap ASME A112.1.2 X — X — See Table 603.3.1 in this chapter.
Air gap fittings for use with plumbing fixtures, appliances, and appurtenances ASME A112.1.3 X — X — Air gap fitting is a device with an internal air gap, and typical installation includes plumbing fixtures, appliances, and appurtenances. The critical level shall not be installed below the flood level rim.
Atmospheric vacuum breaker (consists of a body, checking member and atmospheric port) ASSE 1001 or
CSA B64.1.1
X — X — Upright position. Have outlet open to atmosphere. Minimum of 6 inches or listed distance above all downstream piping and flood level rim of receptor.4,5
Antisiphon fill valve (ballcocks) for gravity water closet flush tanks and urinal tanks ASSE 1002/ ASME A112.1002/ CSA B125.12 X — X — Installation of gravity water closet flush tank and urinal tanks with the fill valve installed with the critical level not less than 1 inch above the opening of the overflow pipe.4,5
Vacuum breaker wall hydrants, hose bibbs, freeze resistant, automatic draining type ASSE 1019 or
CSA B64.2.1.1
X — X — Installation includes wall hydrants and hose bibbs. Such devices are not for use under continuous pressure conditions (means of shutoff downstream of device is prohibited).4,5
Hose connection vacuum breakers ASSE 1011 X — X — Such devices are not for use under continuous pressure conditions. No valve downstream.4,6
Hose connection backflow preventers ASSE 1052 X — X — Such devices are not for use under continuous pressure conditions.4,6
Dual check backflow preventer ASSE 1024 X X — — Installation does not include carbonated drink dispensers.
Dual check backflow preventer wall hydrants, freeze resistant ASSE 1053 X — X — Such devices are not for use under continuous pressure conditions.4
Freeze resistant sanitary yard hydrants ASSE 1057 X — X — Such devices are not for use under continuous pressure conditions.4
Backflow preventer with intermediate atmospheric vent ASSE 1012 X X — — Installation of potable water connections to water boilers. No high-hazard chemicals shall be introduced into the system using such devices. Designed to operate under continuous pressure conditions. May discharge water.
Backflow preventer with intermediate atmospheric vent and pressure reducing valve ASSE 1081 X X — — Installation of potable water connections to water boilers. No high-hazard chemicals shall be introduced into the system using such devices. Designed to operate under continuous pressure conditions. May discharge water.
Backflow preventer for Carbonated Beverage Dispensers (two independent check valves with a vent to the atmosphere) ASSE 1022 X — — — Installation includes carbonated beverage machines or dispensers. These devices operate under intermittent or continuous pressure conditions.
Spill-Resistant Pressure Vacuum Breaker (single check valve with air inlet vent and means of field testing) ASSE 1056 X — X — Upright position. Minimum of 12 inches or listed distance above all downstream piping and flood-level rim of receptor.5
Double Check Valve Backflow Prevention Assembly (two independent check valves and means of field testing) ASSE 1015; AWWA C510; CSA B64.5 or CSA B64.5.1 X X — — Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12 inch clearance at the bottom for maintenance. May need platform/ladder for test and repair.
Does not discharge water.
Double Check Detector Fire Protection Backflow Prevention Assembly (two independent check valves with a parallel detector assembly consisting of a water meter and a double check valve backflow prevention assembly and means for field testing) ASSE 1048 X X — — Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12 inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. Does not discharge water. Installation includes a fire protection system and is designed to operate under continuous pressure conditions.
Pressure Vacuum Breaker Backflow Prevention Assembly (loaded air inlet valve, internally loaded check valve and means for field testing) ASSE 1020 or CSA B64.1.2 X — X — Upright position. May have valves downstream. Minimum of 12 inches above all downstream piping and flood-level rim of the receptor. May discharge water.
Reduced Pressure Principle Backflow Prevention Assembly (two independently acting loaded check valves, a differential pressure relief valve and means for field testing) ASSE 1013; AWWA C511; CSA B64.4 or CSA B64.4.1 X X X X Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12 inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. May discharge water.
Reduced Pressure Detector Fire Protection Backflow Prevention Assembly (two independently acting loaded check valves, a differential pressure relief valve, with a parallel detector assembly consisting of a water meter and a reduced-pressure principle backflow prevention assembly, and means for field testing) ASSE 1047 X X X X Horizontal unless otherwise listed. Access and clearance shall be in accordance with the manufacturer's instructions, and not less than a 12 inch clearance at the bottom for maintenance. May need platform/ladder for test and repair. May discharge water. Installation includes a fire protection system and is designed to operate under continuous pressure conditions.
Laboratory faucet backflow preventer ASSE 1035 — — X X Installation includes laboratory faucets. Such devices are not for use under continuous pressure conditions. No valve downstream.4
For SI units: 1 inch = 25.4 mm
Notes:
1 See the description of devices and assemblies in this chapter.
2 Installation in pit or vault requires previous approval by the Authority Having Jurisdiction.
3 Refer to the general and specific requirement for installation.
4 Not to be subjected to operating pressure for more than 12 hours in a 24 hour period.
5 For deck-mounted and equipment-mounted vacuum breaker, see Section 603.5.13.
6 Shall be installed in accordance with Section 603.5.7.

Related Code Sections


603.2 Water Supply and Distribution, Approval of Devices or Assemblies
Before a device or an assembly is installed for the prevention of backflow, it shall have first been approved by the Authority Having Jurisdiction ...
2021 Oregon Plumbing Specialty Code > 6 Water Supply and Distribution > 603.0 Cross-Connection Control > 603.2 Approval of Devices or Assemblies
P2902.1 Water Supply and Distribution, General
a cross connection between the supply and a source of contamination except where approved backflow prevention assemblies, backflow prevention devices ...
2021 Oregon Residential Specialty Code (ORSC) > 29 Water Supply and Distribution > P2902 Protection of Potable Water Supply > P2902.1 General
711.2.5 Fire and Smoke Protection Features, Ceiling Panels
an upward force of 1 pound per square foot (48 Pa), wire or other approved devices shall be installed above the panels to prevent vertical ...
2019 Oregon Structural Specialty Code (OSSC) > 7 Fire and Smoke Protection Features > 711 Floor and Roof Assemblies > 711.2 Horizontal Assemblies > 711.2.5 Ceiling Panels
(3) Equipment for General Use, Integral With Motor
of an approved assembly that does not normally subject the motor to overloads ...
2021 Oregon Electrical Specialty Code (OESC) > 4 Equipment for General Use > 430 Motors, Motor Circuits, and Controllers > 430.32 Continuous-Duty Motors > (A) More Than 1 Horsepower > (3) Integral With Motor
382.56 Wiring Methods and Materials, Splices and Taps
, connectors, or devices. Taps shall be permitted where approved fittings completely covering the tap connections are used. Aerial cable and its tap connectors ...
2021 Oregon Electrical Specialty Code (OESC) > 3 Wiring Methods and Materials > 382 Nonmetallic Extensions > 382.56 Splices and Taps
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING