// CODE SNIPPET
504.3 Application of Multiple Appliance Vent Tables 504
JUMP TO FULL CODE CHAPTER
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
3(1) through 504.3(8). The application of Tables 504.3(1) through 504.3(8) shall be subject to the requirements of Sections 504.3.1 through 504.3.2.5.
These venting tables shall not be used where obstructions, as described in Section 503.15, are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer's instructions or in accordance with the following:
1. The maximum capacity of the vent connector shall be determined using the NAT Max column.
2. The maximum capacity of the vertical vent or chimney shall be determined using the FANNAT column when the second appliance is a fan-assisted appliance, or the NATNAT column when the second appliance is equipped with a draft hood.
3.1. The minimum capacity of the vent connector shall be determined using the FAN Min column.
3.2. The FANFAN column shall be used where the second appliance is a fan-assisted appliance, and the FANNAT column shall be used where the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized.
The vent connector shall be routed to the vent utilizing the shortest possible route. Except as provided in Section 504.3.3, the maximum vent connector horizontal length shall be 11/2 feet for each inch (18 mm per mm) of connector diameter as shown in Table 504.3.2.
CONNECTOR DIAMETER MAXIMUM (inches) |
CONNECTOR HORIZONTAL LENGTH (feet) |
---|---|
3 | 41/2 |
4 | 6 |
5 | 71/2 |
6 | 9 |
7 | 101/2 |
8 | 12 |
9 | 131/2 |
10 | 15 |
12 | 18 |
14 | 21 |
16 | 24 |
18 | 27 |
20 | 30 |
22 | 33 |
24 | 36 |
Connectors with longer horizontal lengths than those listed in Section 504.3.2 are permitted under the following conditions:
- The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length listed above. For example, the maximum length listed above for a 4-inch (102 mm) connector is 6 feet (1829 mm).With a connector length greater than 6 feet (1829 mm) but not exceeding 12 feet (3658 mm), the maximum capacity must be reduced by 10 percent (0.90 × maximum vent connector capacity). With a connector length greater than 12 feet (3658 mm) but not exceeding 18 feet (5486 mm), the maximum capacity must be reduced by 20 percent (0.80 maximum vent capacity).
- For a connector serving a fan-assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding single appliance table. For Type B double-wall connectors, Table 504.2(1) shall be used. For single-wall connectors, Table 504.2(2) shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single-appliance vent, as if the other appliances were not present.
Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10-percent reduction (0.90 maximum common vent capacity) to the common vent capacity part of the common vent tables. The length of the common vent connector manifold (L M ) shall not exceed 11/2 feet for each inch (457 mm for each 25.4 mm) of common vent connector manifold diameter (D) (see Figure B-11).
For each elbow up to and including 45 degrees (0.79 rad) in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent.
The vent connector capacities listed in the common vent sizing tables include allowance for two 90-degree (1.57 rad) elbows. For each additional elbow up to and including 45 degrees (0.79 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees (0.79 rad) up to and including 90 degrees (1.57 rad), the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent.
At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors.
Connector rise (R) for each appliance connector shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together.
For multiple units of equipment all located on one floor, available total height (H) shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent.
For multistory installations, available total height (H) for each segment of the system shall be the vertical distance between the highest draft hood outlet or flue collar entering that segment and the centerline of the next higher interconnection tee.
The size of the lowest connector and of the vertical vent leading to the lowest interconnection of a multistory system shall be in accordance with Table 504.2(1) or 504.2(2) for available total height (H) up to the lowest interconnection.
Offsets in multistory common vent systems shall be limited to a single offset in each system, and systems with an offset shall comply with all of the following:
1. The offset angle shall not exceed 45 degrees (0.79 rad) from vertical.
2. The horizontal length of the offset shall not exceed 11/2 feet for each inch (457 mm for each 25.4 mm) of common vent diameter of the segment in which the offset is located.
Where two or more appliances are connected to a vertical vent or chimney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area, or draft hood outlet area unless designed in accordance with approved engineering methods.
For appliances with more than one input rate, the minimum vent connector capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined from the tables shall be greater than the highest appliance input rating.
Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 504.3(1) or 504.3(2) for Type B vents, with the maximum capacity reduced by 20 percent (0.80 × maximum capacity) and the minimum capacity as shown in Table 504.3(1) or 504.3(2). Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Sections 504.3.5 and 504.3.6. The 20-percent reduction for corrugated metallic chimney liner systems includes an allowance for one long-radius 90-degree (1.57 rad) turn at the bottom of the liner.
Related Code Sections
504.3 Chimneys and Vents, Application of Multiple Appliance Vent Tables 504
) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined ...
NYC Fuel Gas Code 2008 > 5 Chimneys and Vents > 504 Sizing of Category I Appliance Venting Systems > 504.3 Application of Multiple Appliance Vent Tables 504
504.3.11 Chimneys and Vents, Vent Height Measurement
For multiple units of equipment all located on one floor, available total height (H) shall be measured from the highest draft hood outlet or flue ...
NYC Fuel Gas Code 2008 > 5 Chimneys and Vents > 504 Sizing of Category I Appliance Venting Systems > 504.3 Application of Multiple Appliance Vent Tables 504 > 504.3.11 Vent Height Measurement
504.3.7 Chimneys and Vents, Elbows in Connectors
The vent connector capacities listed in the common vent sizing tables include allowance for two 90-degree (1.57 rad) elbows. For each additional ...
NYC Fuel Gas Code 2008 > 5 Chimneys and Vents > 504 Sizing of Category I Appliance Venting Systems > 504.3 Application of Multiple Appliance Vent Tables 504 > 504.3.7 Elbows in Connectors
504.3.20 Chimneys and Vents, Connector Maximum and Minimum Size
a vent connector size(s) determined from the tables for a fan-assisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size ...
NYC Fuel Gas Code 2008 > 5 Chimneys and Vents > 504 Sizing of Category I Appliance Venting Systems > 504.3 Application of Multiple Appliance Vent Tables 504 > 504.3.20 Connector Maximum and Minimum Size
504.3.24 Chimneys and Vents, Extrapolation Prohibited
Extrapolation beyond the table entries shall not be permitted ...
NYC Fuel Gas Code 2008 > 5 Chimneys and Vents > 504 Sizing of Category I Appliance Venting Systems > 504.3 Application of Multiple Appliance Vent Tables 504 > 504.3.24 Extrapolation Prohibited