[F] 416.1 General
The provisions of this section shall apply to the construction, installation and use of buildings and structures, or parts thereof, for the application of flammable finishes. Such construction and equipment shall comply with the International Fire Code.
[F] 416.2 Spray Rooms
Spray rooms shall be enclosed with not less than 1-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Floors shall be waterproofed and drained in an approved manner.
[F] 416.2.1 Surfaces
The interior surfaces of spray rooms shall be smooth and shall be so constructed to permit the free passage of exhaust air from all parts of the interior and to facilitate washing and cleaning, and shall be so designed to confine residues within the room. Aluminum shall not be used.
[F] 416.2.2 Ventilation
Mechanical ventilation and interlocks with the spraying operation shall be in accordance with the International Mechanical Code.
[F] 416.3 Spraying Spaces
Spraying spaces shall be ventilated with an exhaust system to prevent the accumulation of flammable mist or vapors in accordance with the International Mechanical Code. Where such spaces are not separately enclosed, noncombustible spray curtains shall be provided to restrict the spread of flammable vapors.
[F] 416.3.1 Surfaces
The interior surfaces of spraying spaces shall be smooth and continuous without edges; shall be so constructed to permit the free passage of exhaust air from all parts of the interior and to facilitate washing and cleaning; and shall be so designed to confine residues within the spraying space. Aluminum shall not be used.
[F] 416.4 Spray Booths
Spray booths shall be designed, constructed and operated in accordance with the International Fire Code.
[F] 416.5 Fire Protection
An automatic sprinkler system or fire-extinguishing system shall be provided in all spray, dip and immersing spaces and storage rooms and shall be installed in accordance with Chapter 9.

Related Code Sections

Section 416 Special Detailed Requirements Based on Use and Occupancy, Application of Flammable Finishes
of flammable paints, varnishes and lacquers or other flammable materials or mixtures or compounds used for painting, varnishing, staining or similar ...
502.7 Exhaust Systems, Application of Flammable Finishes
Mechanical exhaust as required by this section shall be provided for operations involving the application of flammable finishes ...
502.7 Exhaust Systems, Application of Flammable Finishes
Mechanical exhaust as required by this section shall be provided for operations involving the application of flammable finishes ...
502.7 Exhaust Systems, Application of Flammable Finishes
Mechanical exhaust as required by this section shall be provided for operations involving the application of flammable finishes ...