The text of Section 6.2.2 of ASTM E 1996 shall be substituted as follows:
6.2.2 Unless otherwise specified, select the wind zone based on the strength design wind speed, Vult, as follows:
6.2.2.1 Wind Zone 1—130 mph ≤ ultimate design wind speed, Vult< 140 mph.
6.2.2.2 Wind Zone 2—140 mph ≤ ultimate design wind speed, Vult< 150 mph at greater than one mile (1.6 km) from the coastline. The coastline shall be measured from the mean high water mark.
6.2.2.3 Wind Zone 3—150 mph (58 m/s) ≤ ultimate design wind speed, Vult ≤ 160 mph (63 m/s), or 140 mph (54 m/s) ≤ ultimate design wind speed, Vult ≤ 160 mph (63 m/s) and within one mile(1.6 km) of the coastline. The coastline shall be measured from the mean high water mark.
6.2.2.4 Wind Zone 4— ultimate design wind speed, Vult >160 mph (63 m/s).