1311.6 Appliance Overpressure Protection
JUMP TO FULL CODE CHAPTER
The maximum operating pressure for piping systems serving appliances
designed to operate at 14 inches water column (3.5 kPa) inlet
pressure or less shall be 2 pounds-force per square inch gauge
(psig) (14 kPa) unless an overpressure protection device
designed to limit pressure at the appliance to 2 psig (14 kPa)
upon failure of the line gas pressure regulator is installed.
Related Code Sections
1310.6 Fuel Gas Piping, Appliance Overpressure Protection
shall be 2 pounds-force per square inch
gauge (psig) (14 kPa) unless an over pressure protection
device designed to limit pressure at the appliance ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1310.0 Gas Piping Installation > 1310.6 Appliance Overpressure Protection
1311.6 Fuel Gas Piping, Appliance Overpressure Protection
shall be 2 pounds-force per square inch gauge
(psig) (14 kPa) unless an overpressure protection device
designed to limit pressure at the appliance to 2 ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1311.0 Gas Piping Installation > 1311.6 Appliance Overpressure Protection
1308.8 Fuel Gas Piping, Overpressure Protection
at inlet pressures greater than
14 inches water column (3.5 kPa) shall be equipped with
overpressure protection devices as required by the appliance ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1308.0 Gas Piping System Design, Materials, and Components > 1308.8 Overpressure Protection
1208.9 Fuel Gas Piping, Overpressure Protection Devices
pressure of 14 inches water column (3.5 kPa) or less,
overpressure protection devices shall be installed. Piping systems serving equipment designed ...
Los Angeles Plumbing Code > 12 Fuel Gas Piping > 1208.0 Gas Piping System Design, Materials, and Components > 1208.9 Overpressure Protection Devices
1308.9.2 Fuel Gas Piping, Overpressure Protection Devices
Each
overpressure protection device installed to meet the
requirements of this section shall be capable of limiting
the pressure to its connected ...
Los Angeles Mechanical Code > 13 Fuel Gas Piping > 1308.0 Gas Piping System Design, Materials, and Components > 1308.9 Pressure Limitation Requirements > 1308.9.2 Overpressure Protection Devices