M1307.1 General
Installation of appliances shall conform to the conditions of their listing and label and the manufacturer's instructions. The manufacturer's operating and installation instructions shall remain attached to the appliance.
M1307.2 Anchorage of Appliances
Appliances designed to be fixed in position shall be fastened or anchored in an approved manner. In Seismic Design Categories D0, D1 and D2, and in townhouses in Seismic Design Category C, water heaters and thermal storage units shall be anchored or strapped to resist horizontal displacement caused by earthquake motion in accordance with one of the following:
  1. Anchorage and strapping shall be designed to resist a horizontal force equal to one-third of the operating weight of the water heater storage tank, acting in any horizontal direction. Strapping shall be at points within the upper one-third and lower one-third of the appliance's vertical dimensions. At the lower point, the strapping shall maintain a minimum distance of 4 inches (102 mm) above the controls.
  2. The anchorage strapping shall be in accordance with the appliance manufacturer's recommendations.
M1307.3 Elevation of Ignition Source
Appliances having an ignition source shall be elevated such that the source of ignition is not less than 18 inches (457 mm) above the floor in garages. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate with a private garage through openings shall be considered to be part of the garage.
Exception: Elevation of the ignition source is not required for appliances that are listed as flammable-vapor-ignition resistant.
M1307.3.1 Protection From Impact
Appliances shall not be installed in a location subject to vehicle damage except where protected by approved barriers.
M1307.4 Hydrogen-Generating and Refueling Operations
Ventilation shall be required in accordance with Section M1307.4.1, M1307.4.2 or M1307.4.3 in private garages that contain hydrogen-generating appliances or refueling systems. For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate directly with a private garage through openings shall be considered to be part of the private garage.
M1307.4.1 Natural Ventilation
Indoor locations intended for hydrogen-generating or refueling operations shall be limited to a maximum floor area of 850 square feet (79 m2) and shall communicate with the outdoors in accordance with Sections M1307.4.1.1 and M1307.4.1.2. The maximum rated output capacity of hydrogen-generating appliances shall not exceed 4 standard cubic feet per minute (1.9 L/s) of hydrogen for each 250 square feet (23 m2) of floor area in such spaces. The minimum cross-sectional dimension of air openings shall be 3 inches (76 mm). Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. In those locations, equipment and appliances having an ignition source shall be located so that the source of ignition is not within 12 inches (305 mm) of the ceiling.
M1307.4.1.1 Two Openings
Two permanent openings shall be constructed within the garage. The upper opening shall be located entirely within 12 inches (305 mm) of the ceiling of the garage. The lower opening shall be located entirely within 12 inches (305 mm) of the floor of the garage. Both openings shall be constructed in the same exterior wall. The openings shall communicate directly with the outdoors and shall have a minimum free area of 1/2 square foot per 1,000 cubic feet (1.7 m2/1000 m3) of garage volume.
M1307.4.1.2 Louvers and Grilles
In calculating free area required by Section M1307.4.1, the required size of openings shall be based on the net free area of each opening. If the free area through a design of louver or grille is known, it shall be used in calculating the size opening required to provide the free area specified. If the design and free area are not known, it shall be assumed that wood louvers will have a 25-percent free area and metal louvers and grilles will have a 75-percent free area. Louvers and grilles shall be fixed in the open position.
M1307.4.2 Mechanical Ventilation
Indoor locations intended for hydrogen-generating or refueling operations shall be ventilated in accordance with Section 502.16 of the International Mechanical Code. In these locations, equipment and appliances having an ignition source shall be located so that the source of ignition is below the mechanical ventilation outlet(s).
M1307.4.3 Specially Engineered Installations
As an alternative to the provisions of Sections M1307.4.1 and M1307.4.2, the necessary supply of air for ventilation and dilution of flammable gases shall be provided by an approved engineered system.
M1307.5 Electrical Appliances
Electrical appliances shall be installed in accordance with Chapters 14, 15, 19, 20 and 34 through 43.
M1307.6 Plumbing Connections
Potable water and drainage system connections to equipment and appliances regulated by this code shall be in accordance with Chapters 29 and 30.
M1307.7 Prohibited Support
Gypsum board shall not be used as a support base under an appliance.

Related Code Sections

Chapter 41 Appliance Installation
ICC user note: About this chapter: Chapter 41 covers appliance installation, which is typically the final stage of construction after all wiring ...
Section M1307 General Mechanical System Requirements, Appliance Installation
Installation of appliances shall conform to the conditions of their listing and label and the manufacturer's instructions. The manufacturer's ...
Section E4101 Appliance Installation, General
This section covers installation requirements for appliances and fixed heating equipment. (422.1 and 424.1 ...