UpCodes logo
// CODE SNIPPET

Section G2422 (411) Appliance Connections

Go To Full Code Chapter
G2422.1 (411.1) Connecting Appliances
Appliances shall be connected to the piping system by one of the following:
  1. Rigid metallic pipe and fittings.
  2. Corrugated stainless steel tubing (CSST) where installed in accordance with the manufacturer's instructions.
  3. Listed and labeled appliance connectors in compliance with ANSI Z21.24/CSA 6.10 and installed in accordance with the manufacturer's instructions and located entirely in the same room as the appliance.
  4. Listed and labeled quick-disconnect devices in compliance with ANSI Z21.41/CSA 6.9 used in conjunction with listed and labeled appliance connectors.
  5. Listed and labeled convenience outlets in compliance with ANSI Z21.90/CSA 6.24 used in conjunction with listed and labeled appliance connectors.
  6. Listed and labeled outdoor appliance connectors in compliance with ANSI Z21.75/CSA 6.27 and installed in accordance with the manufacturer's instructions.
  7. Listed outdoor gas hose connectors in compliance with ANSI Z21.54 used to connect portable outdoor appliances. The gas hose connection shall be made only in the outdoor area where the appliance is used, and shall be to the gas piping supply at an appliance shutoff valve, a listed quick-disconnect device or listed gas convenience outlet.
G2422.1.1 (411.1.2) Protection From Damage
Connectors and tubing shall be installed so as to be protected against physical damage.
G2422.1.2 (411.1.3) Connector Installation
Appliance fuel connectors shall be installed in accordance with the manufacturer's instructions and Sections G2422.1.2.1 through G2422.1.2.4.
G2422.1.2.1 (411.1.3.1) Maximum Length
Connectors shall have an overall length not to exceed 6 feet (1829 mm). Measurement shall be made along the centerline of the connector. Only one connector shall be used for each appliance.
Exception: Rigid metallic piping used to connect an appliance to the piping system shall be permitted to have a total length greater than 6 feet (1829 mm), provided that the connecting pipe is sized as part of the piping system in accordance with Section G2413 and the location of the appliance shutoff valve complies with Section G2420.5.
G2422.1.2.2 (411.1.3.2) Minimum Size
Connectors shall have the capacity for the total demand of the connected appliance.
G2422.1.2.3 (411.1.3.3) Prohibited Locations and Penetrations
Connectors shall not be concealed within, or extended through, walls, floors, partitions, ceilings or appliance housings.

Exceptions:
  1. Connectors constructed of materials allowed for piping systems in accordance with Section G2414 shall be permitted to pass through walls, floors, partitions and ceilings where installed in accordance with Section G2420.5.2 or G2420.5.3.
  2. Rigid steel pipe connectors shall be permitted to extend through openings in appliance housings.
  3. Fireplace inserts that are factory equipped with grommets, sleeves or other means of protection in accordance with the listing of the appliance.
  4. Semirigid tubing and listed connectors shall be permitted to extend through an opening in an appliance housing, cabinet or casing where the tubing or connector is protected against damage.
G2422.1.2.4 (411.1.3.4) Shutoff Valve
A shutoff valve not less than the nominal size of the connector shall be installed ahead of the connector in accordance with Section G2420.5.
G2422.1.3 (411.1.5) Connection of Gas Engine-Powered Air Conditioners
Internal combustion engines shall not be rigidly connected to the gas supply piping.
G2422.1.4 (411.1.6) Unions
A union fitting shall be provided for appliances connected by rigid metallic pipe. Such unions shall be accessible and located within 6 feet (1829 mm) of the appliance.
G2422.1.5 (411.1.4) Movable Appliances
Where appliances are equipped with casters or are otherwise subject to periodic movement or relocation for purposes such as routine cleaning and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69/CSA 6.16 or by means of Item 1 of Section G2422.1. Such flexible connectors shall be installed and protected against physical damage in accordance with the manufacturer's instructions.
G2422.2 (411.3) Suspended Low-Intensity Infrared Tube Heaters
Suspended low-intensity infrared tube heaters shall be connected to the building piping system with a connector listed for the application complying with ANSI Z21.24/CSA 6.10. The connector shall be installed as specified by the tube heater manufacturer's instructions.

Related Code Sections

Section G2422 Fuel Gas, (411) Appliance Connections
Appliances shall be connected to the piping system by one of the following: Rigid metallic pipe and fittings. Corrugated stainless steel tubing ...
Section G2422 Fuel Gas, (411) Appliance Connections
Appliances shall be connected to the piping system by one of the following: Rigid metallic pipe and fittings. Corrugated stainless steel tubing ...
G2422.1.5 Fuel Gas, (411.1.4) Movable Appliances
and maintenance, such appliances shall be connected to the supply system piping by means of an appliance connector listed as complying with ANSI Z21.69/CSA ...