// CODE SNIPPET
13.6.4.3.2 Annual External Examination of All Extinguishers
Go To Full Code Chapter
13.6.4.3.2.1 Physical Condition
An annual external visual examination of all fire extinguishers shall be made to detect obvious physical damage, corrosion, or nozzle blockage; to verify that the operating instructions are present, legible, and facing forward, and that the HMIS information is present and legible, and to determine if a 6-year interval examination or hydrostatic test is due. [10:7.3.2.1]
13.6.4.3.2.2* Seals or Tamper Indicators
At the time of the maintenance, the tamper seal of a rechargeable fire extinguisher shall be removed by operating the pull pin or locking device. [10:7.3.2.2]
13.6.4.3.2.2.1
After the applicable maintenance procedures are completed, a new listed tamper seal shall be installed. [10:7.3.2.2.1]
13.6.4.3.2.2.2
Seals or tamper indicators on nonrechargeable-type extinguishers shall not be removed. [10:7.3.2.2.2]
13.6.4.3.2.3* Boots, Foot Rings, and Attachments
All removable extinguisher boots, foot rings, and attachments shall be removed to accommodate thorough annual cylinder examinations. [10:7.3.2.3]
13.6.4.3.2.4
When subjected to temperatures at or above their listed rating, stored-pressure fire extinguishers that require a 12-year hydrostatic test shall be emptied and subjected to the applicable maintenance and recharge procedures on an annual basis. [10:7.3.2.4]
13.6.4.3.2.5 Corrective Action
When an external examination of any fire extinguisher reveals a deficiency, immediate corrective action shall be taken. [10:7.3.2.5]
Related Code Sections
13.6.4.3.2 Fire Protection Systems, Annual External Examination of All Extinguishers
An annual external visual examination of all fire extinguishers shall be made to detect obvious physical damage, corrosion, or nozzle blockage ...
13.6.4.3.2.2.1 Fire Protection Systems,
After the applicable maintenance procedures are completed, a new listed tamper seal shall be installed. [10:7.3.2.2.1 ...
13.6.4.3.2.2.2 Fire Protection Systems,
Seals or tamper indicators on nonrechargeable-type extinguishers shall not be removed. [10:7.3.2.2.2] ...
13.6.4.3 Fire Protection Systems, Extinguisher Maintenance
annual external visual examination of all fire extinguishers shall be made to detect obvious physical damage, corrosion, or nozzle blockage ...
13.6.4 Fire Protection Systems, Inspection, Maintenance, and Recharging
annual external visual examination of all fire extinguishers shall be made to detect obvious physical damage, corrosion, or nozzle ...