1405.6 Anchored Masonry Veneer
JUMP TO FULL CODE CHAPTER
Anchored masonry veneer shall comply with the provisions of Sections 1405.6, 1405.7, 1405.8, and 1405.9 and Sections 6.1 and 6.2 of TMS 402/ACI 530/ASCE 5.
Anchored masonry veneers in accordance with Chapter 14 are not required to meet the tolerances in Article 3.3 G1 of TMS 602/ACI 530.1/ASCE 6.
Anchored masonry veneer located in Seismic Design Category C or D shall conform to the requirements of Section 6.2.2.10 of TMS 402/ACI 530/ASCE 5. Anchored masonry veneer located in Seismic Design Category D shall also conform to the requirements of Section 6.2.2.10.3.3 of TMS 402/ACI 530/ASCE 5.
Related Code Sections
1405.5 Exterior Walls, Anchored Masonry Veneer
Anchored masonry veneer shall comply with the provisions of Sections 1405.5, 1405.6, 1405.7 and 1405.8 and Sections 6.1 and 6.2 of ACI 530/ASCE 5/TMS ...
NYC Building Code 2008 > 14 Exterior Walls > 1405 Installation of Wall Coverings > 1405.5 Anchored Masonry Veneer
1405.6 Exterior Walls, Anchored Masonry Veneer
Anchored masonry veneer shall comply with the provisions of Sections 1405.6, 1405.7, 1405.8, and 1405.9 and Sections 6.1 and 6.2 of TMS 402/ACI 530 ...
NYC Building Code 2014 > 14 Exterior Walls > 1405 Installation of Wall Coverings > 1405.6 Anchored Masonry Veneer
1404.4 Exterior Walls, Masonry
and metal accessories used in anchored and adhered veneer shall meet the physical requirements of Chapter 21. The backing of anchored and adhered veneer ...
1404.4 Exterior Walls, Masonry
and metal accessories used in anchored and adhered veneer shall meet the physical requirements of Chapter 21. The backing of anchored and adhered veneer ...
Reference Standard 10 Structural Work [PDF] (page 16)
of Veneer Anchored Type: Solid masonry units…... Hollow masonry units... Ceramic veneer……….. Adhesion Type: Solid masonry units…... Ceramic veneer ...