Concrete or masonry walls shall be anchored to floors and roofs and members that provide out-of-plane lateral support for the wall or that are supported by the wall. The anchorage shall provide a positive direct connection between the wall and floor or roof capable of resisting the horizontal forces specified in Equation 16-62 for structures with flexible diaphragms or in Section 9.6.1.3 of ASCE 7 (using ap of 1.0 and Rp of 2.5) for structures with diaphragms that are not flexible.

Fp = 0.8 SDSIEww              (Equation 16-62)

where:

Fp = The design force in the individual anchors.
IE = Occupancy importance factor in accordance with Section 1616.2.
SDS = The design earthquake spectral response acceleration at short period in accordance with Section 1615.1.3.
ww = The weight of the wall tributary to the anchor.


   Diaphragms shall be provided with continuous ties or struts between diaphragm chords to distribute these anchorage forces into the diaphragms. Where added chords are used to form subdiaphragms, such chords shall transmit the anchorage forces to the main cross ties. The maximum length-to-width ratio of the structural subdiaphragm shall be 21/2 to 1. Connections and anchorages capable of resisting the prescribed forces shall be provided between the diaphragm and the attached components. Connections shall extend into the diaphragms a sufficient distance to develop the force transferred into the diaphragm.

   The strength design forces for steel elements of the wall anchorage system shall be 1.4 times the force otherwise required by this section.

   In wood diaphragms, the continuous ties shall be in addition to the diaphragm sheathing. Anchorage shall not be accomplished by use of toenails or nails subject to withdrawal, nor shall wood ledgers or framing be used in cross-grain bending or cross-grain tension. The diaphragm sheathing shall not be considered effective as providing the ties or struts required by this section.

   In metal deck diaphragms, the metal deck shall not be used as the continuous ties required by this section in the direction perpendicular to the deck span.

   Diaphragm-to-wall anchorage using embedded straps shall be attached to or hooked around the reinforcing steel or otherwise terminated so as to directly transfer force to the reinforcing steel.

Related Code Sections

Reference Standard 9 Loads [PDF] (page 12)
, be intermediate moment-resisting frames, except as noted in Table 23-0." Paragraph 2, subparagraph H, Anchorage of concrete or masonry walls. Delete ...
2308.6.7.3 Wood, Sill Anchorage
Where foundations are required by Section 2308.6.8, braced wall line sills shall be anchored to concrete or masonry foundations. Such anchorage shall ...
2308.3.3 Wood, Sill Anchorage
Where foundations are required by Section 2308.3.4, braced wall line sills shall be anchored to concrete or masonry foundations. Such anchorage shall ...
2308.3.3 Wood, Sill Anchorage
Where foundations are required by Section 2308.3.4, braced wall line sills shall be anchored to concrete or masonry foundations. Such anchorage shall ...